Remove Fan And Cover; Convection Cooling - U-Line 2224BEV User Manual & Service Manual

2000 series 24" beverage center
Hide thumbs Also See for 2224BEV:
Table of Contents

Advertisement

USER GUIDE
SAFETY • INSTALLATION & INTEGRATION • OPERATING INSTRUCTIONS • MAINTENANCE • SERVICE
Defrost
The models below have automatic or frost free design and do not require manual defrosting under normal
conditions.
Base Model
1224
1215/1224/2218/2245/
2224/2260
1215/1224/2218/2245/
2224/2260
CO29
CO1224
1224FZR
1224FZR
The defrost settings for 3000 series models are determined by zone.
Zones
Beverage/Drinks
Market/Fresh
Root/Root Cellar
Pantry
White Wine
Red Wine
Sparkling Wine
Polar
Deli

Remove Fan and Cover

CONVECTION COOLING

This unit is equipped with an advanced convection
cooling system. Convection cooling stabilizes cabinet
temperature, cools product faster and increases
energy efficiency.
Defrost Settings
Variant(s)
Compressor Run Time
Between Defrost (Hours)
RF
WC, ZWC
R, RSOD, RDC,
BEV, DC, DWR,
RGL
F
F
Freezer Mode
Refrigerator Mode
Defrost Settings by Zone (3000 Series)
Compressor Run Time
Between Defrost (Hours)
12
12
12
12
12
12
12
6
12
Duration in Minutes
12
12
12
12
12
6
12
Duration in Minutes
Duration in Minutes
(Minimum)
5
5
5
5
5
5
5
5
5
Evaporator Fan
The evaporator fan is responsible for circulating warm
air from the refrigeration zone, past the evaporator
and back into the refrigerated zone.
The evaporator fan is factory set to have a 1 minute
delay at the beginning of a cooling cycle. This delay
gives the evaporator time to cool properly before
warm air is passed over it. The fan will continue to run
for an additional 2 minutes at the end of a cooling
Stop Temperature
(Maximum)
°F (°C)
45
15 (-9)
45
45 (7)
45
42 (6)
18
18
45 (7)
45
42(6)
45
42(6)
Stop Temperature
(Maximum)
°F (°C)
60
42 (6)
60
42 (6)
60
45 (7)
60
42 (6)
60
45 (7)
60
45 (7)
60
45 (7)
20
42 (6)
60
42 (6)
u-line.com
Thermistor 2
n/a
Defrost 1