Control level 3 - Specialist - System parameters
Parameter
LM100
Cascade effect
LM101
Integral action time for cascade
LM102
Supply air maximum limit
LM103
Control type
LM114
Damper lead time
LM130
Night ventilation limit
LM131
Night ventilation start condition
differential TR > TA
LM132
Night ventilation, minimum
outside temperature
LM150
P component for HR
LM151
Integral action time for HR
LM160
Air quality control
LM161
Air quality, start
LM162
Air quality, maximum
LM163
System OFF/ON via air quality
LM180
Alarm function, fire dampers
LM190
Delay for
air flow fault
LM200
Active filter monitor
LM201
Filter check interval
LM202
Service message
via hours run
LM203
Fan hours run
LM204
Filter check
3063527_201308
Setting
range
0 - 20
0 - 25 min
20 - 60 °C
Supply air control,
cascade control
0 - 150 s
10 - 30 °C
2 K - 20 K
5 - 20 °C
5 - 20
0 - 25 min
OFF/ON
0 - 10 V
0 - 10 V
OFF/ON
(OFF) System
System OFF
Off
(ON) Message
only
5 - 600 s
ON/OFF
1 -10 weeks
ON/OFF
100 - 8000
ON/OFF
Factory
Individual
setting
settings
2
2 min
50 °C
Supply air
control
120 s
22 °C
5 K
12 °C
12
2 min
ON
4 V
8 V
OFF
60 s
OFF
1 week
OFF
1000
OFF
27