Setting Up The Energy Metering - Daikin EWAQ006BAVP Installer's Reference Manual

Packaged air-cooled water chillers and packaged air to water heat pumps
Hide thumbs Also See for EWAQ006BAVP:
Table of Contents

Advertisement

a
b
c
d
e
d
f
h
g
a
Outdoor unit
b
Heat exchanger
c
Pump
d
Shut‑off valve
e
Backup heater (option)
f
Control box
g
User interface
h
Option box
i
Non‑return valve (field supply)
j
Shut‑off valve (field supply)
k
Collector (field supply)
l
Auxiliary boiler (field supply)
m
Aquastat valve (field supply)
FHL1...3
Under floor heating
NOTICE
▪ Make sure the auxiliary boiler and its integration in the
system complies with applicable legislation.
▪ Daikin is NOT responsible for incorrect or unsafe
situations in the auxiliary boiler system.
▪ Make sure the return water to the heat  pump does NOT exceed
55°C. To do so:
▪ Set the desired water temperature via the auxiliary boiler
controller to maximum 55°C.
▪ Install an aquastat valve in the return water flow of the
heat pump.
▪ Set the aquastat valve to close above 55°C and to open below
55°C.
▪ Install non-return valves.
▪ Make sure to only have one expansion vessel in the water circuit.
An expansion vessel is already pre-mounted in the outdoor unit.
▪ Install control box EKCB07CAV3 and option box EK2CB07CAV3.
▪ Connect X8M/3 and X8M/4 (changeover to external heat source)
on option box EK2CB07CAV3 to the auxiliary boiler thermostat.
▪ To setup the heat emitters, see
cooling system" on
page 12.
Configuration
Via the user interface (quick wizard):
▪ Set the use of a bivalent system as external heat source.
▪ Set the bivalent temperature and hysteresis.
EWAQ+EWYQ006+008BAVP + EK(2)CB07CAV3 +
EKMBUHCA3V3+9W1
Packaged air-cooled water chillers and packaged air to water heat
pumps
4P492901-1 – 2017.06
i
k
i
j
l
j
m
FHL1
FHL2
FHL3
"5.2 Setting up the space heating/
5 Application guidelines
NOTICE
▪ Make sure the bivalent hysteresis has enough
differential to prevent frequent changeover between
outdoor unit and auxiliary boiler.
▪ Because the outdoor temperature is measured by the
outdoor unit air thermistor, install the outdoor unit in the
shadow so that it is NOT influenced or turned ON/OFF
by direct sunlight.
▪ Frequent changeover may cause corrosion of the
auxiliary boiler. Contact the manufacturer of the
auxiliary boiler for more information.
Changeover to external heat source decided by an auxiliary
contact
▪ Only possible in external room thermostat control AND one
leaving water temperature zone (see
heating/cooling system" on
page 12).
▪ The auxiliary contact can be:
▪ An outdoor temperature thermostat
▪ An electricity tariff contact
▪ A manually operated contact
▪ ...
▪ Setup: Connect the following field wiring:
L
Com
H
Outdoor/Auto/Boiler
A
K1A
K2A
N
B
Boiler thermostat input
TI
A
Auxiliary contact (normal closed)
H
Heating demand room thermostat (optional)
K1A
Auxiliary relay for activation of outdoor unit (field supply)
K2A
Auxiliary relay for activation of boiler (field supply)
Outdoor
Outdoor unit
Auto
Automatic
Boiler
Boiler
Control box
Control box
NOTICE
▪ Make sure the auxiliary contact has enough differential
or time delay to prevent frequent changeover between
outdoor unit and auxiliary boiler.
▪ If the auxiliary contact is an outdoor temperature
thermostat, install the thermostat in the shadow so that
it is NOT influenced or turned ON/OFF by direct
sunlight.
▪ Frequent changeover may cause corrosion of the
auxiliary boiler. Contact the manufacturer of the
auxiliary boiler for more information.
5.4

Setting up the energy metering

▪ Via the user interface, you can read out the following energy data:
▪ Produced heat
▪ Consumed energy
▪ You can read out the energy data:
▪ For space cooling
▪ For space heating
"5.2  Setting up the space
Control box
B TI
X2M
1 4
X Y
K1A
K2A
Installer reference guide
17