HAZARDOUS LOCATIONS INSTALLATION REQUIREMENTS (UL/CSA/FM)
To reduce the risk of ignition of hazardous atmospheres, conduit runs must have a
pour gland installed within 18 inches (457mm) of enclosure.
All ¾ inch NPT conduit, stopping plugs and adapters must be installed with 5 ¼
threads (minimum) engaged to Maintain Explosion Proof rating.
The XNX Cover Assembly must be fully seated to enclosure 9 threads (minimum)
to maintain Explosion Proof rating.
Stopping Plugs supplied (Honeywell Part Number 1226-0258) are approved for
use ONLY with the XNX Universal Transmitter.
For units fitted with the optional relay module: Relay contact ratings are 250 VAC
5A, 24 VDC 5A Resistive Loads Only.
Use copper conductors only, 60/75°C. Terminal block screws should be tightened
to 4.5 lb/in maximum.
For models XNX-UT**-*****, refer to XNX control drawing 1226E0402 or, for
models
XNX-BT**-*****, refer to control drawing 1226E0454 for additional information
regarding IS function (local HART and EC personalities).
XNX Universal Transmitters carrying UL/CSA/FM approvals that are configured
for devices measuring %LEL will not allow adjustments to the full scale value. The
range is fixed at 100%.
HAZARDOUS LOCATIONS INSTALLATION REQUIREMENTS (ATEX)
Read and understand Technical Manual 1998M0738 before installation and use.
Use only Certified M25 cable glands for installation.
Shielded armoured cable is required for CE compliance.
Special conditions for safe use
The following applies to the HART Barrier intrinsically safe circuits: For
installations in which both the Ci and Li of the intrinsically safe apparatus
exceeds 1% of the Co and Lo parameters of the associated apparatus
(excluding the cable), then 50% of Co and Lo parameters are applicable and
shall not be exceeded, i.e. the Ci of the device plus the C of the cable must be
less than or equal to 50% of the Co of the associated apparatus, and the Li of
the device plus the L of the cable must be less than or equal to 50% of the Lo
of the associated apparatus.
For circuits connected to the EC barrier in which the capacitance and
inductance exceed 1% of the permitted values, then the maximum permitted
capacitance is limited to 600nF for group IIC and 1uF for group IIIC.
The connection to the HART circuit shall be rated a minimum of IP 6X.