S1 RELAY SETUP

S1 Relay setup

Clock

6–6
Figure 6-2: Relay Setup menu
The 350 relay has an internal real time clock that performs time stamping via IRIG-B for
various features such as the event and transient recorders. This time stamping is available
with the IRIG-B signal connected to the relay terminals and set to "Enabled". When an IRIG-
B device is connected to the relay terminals, the relay detects the DC shift or the Amplitude
Modulated signal automatically. Time stamping on multiple relays can be synchronized to
± 1.0 ms with the use of IRIG-B input. Time stamping is also optionally available using SNTP.
Time synchronization priority uses the IRIG-B and SNTP protocols - via Modbus, IEC60870-
5-103, IEC60870-5-104, or DNP commands - as follows:
IRIG-B has the highest priority, so any other source of synchronization should be rejected if
IRIG-B is the synchronization source and an IRIG-B signal is available.
PTP (V2) has the second highest priority, so if IRIG-B is not the synchronization source but
PTP is, then any other source of synchronization should be rejected. SNTP has the third
highest priority.
Synchronization commands are all eventually translated into a MODBUS function, and as
such are blocked from the MODBUS layer as required.
Any synchronization commands other than Modbus, IEC60870-5-103, IEC60870-5-104, or
DNP will be accepted only if IRIG-B, PTP, and SNTP are not the synchronization sources.
There is no prioritization amongst synchronization commands. A synchronization
command issued from DNP for example, can be directly followed by another from
MODBUS, for example.
The following path is available using the keypad. For instructions on how to use the
keypad, please refer to Chapter 3 - Working with the Keypad.
PATH:
SETPOINTS > S1 RELAY SETUP > CLOCK
DATE: (MM/DD/YYYY)
Range: Month: Jan, Feb, Mar, Apr, May, Jun, Jul, Aug, Sep, Oct, Nov, Dec Day: 1 to 31 Year:
2009 to 2099
Default: Jan 15 2009
This setting sets the date in the specified format.
TIME: (HH:MM:SS)
Range: 0 to 23: 0 to 59: 0 to59
Default: 03:15:50
This setting sets the time in the specified format.
S1 RELAY SETUP
CLOCK
PASSWORD SECURITY
COMMUNICATIONS
EVENT RECORDER
TRANSIENT RECDR
FAULT REPORT
FRONT PANEL
INSTALLATION
898764A4.cdr