The filled out label must be adhered on the inside of the product and
in the proximity of the product charging port (e.g. on the inside of the
service cover).
6
5
1 factory refrigerant charge of the product:
see unit name plate
2 additional refrigerant
amount charged in the field
3 total refrigerant charge
4 Contains fluorinated greenhouse gases covered by the
Kyoto Protocol
5 outdoor unit
6 refrigerant cylinder and manifold for charging
NOTICE
National implementation of EU regulation on certain
fluorinated greenhouse gases may require to provide the
appropriate official national language on the unit.
Therefore,
an
additional
greenhouse gases label is supplied with the unit.
Sticking instructions are illustrated on the backside of that
label.
10.11.

3 procedures for adding refrigerant

Procedure 1: Adding refrigerant by using the automatic
refrigerant charging function (recommended)
How to connect the tank?
Y1
8
5
4
6
1 2
7
3
1 Liquid stop valve
2 Gas line stop valve
3 To indoor unit
4 Service port for adding refrigerant
5 Valve A
6 R410A tank
7 Measuring instrument
8 Pipe fixing plate
When the refrigerant tank is connected and the specified operation is
performed, the appropriate amount of refrigerant will be charged into
the system. After charging, the system will stop automatically. The
refrigerant must be charged according to the procedure described
below.
Installation manual
12
4
1
2
3
multilingual
fluorinated
CAUTION
Make sure to turn ON the power 6 hours before
starting the operation. This is necessary to warm the
crankcase by the electric heater.
Automatic charging is able to charge 6 kg/hour
refrigerant at an outside temperature of 0°C to 24 kg/
hour refrigerant at an outside temperature of 35°C.
The charging time depends on the amount of charged
refrigerant and on the outside temperature.
Automatic refrigerant charging is NOT possible if the
following restrictions are exceeded:
 Outside temperature: 0°C DB~43°C DB
 Indoor temperature: 0°C DB~32°C DB
 Indoor unit connection capacity: 50%~110%
Automatic refrigerant charging procedure
1
Open the liquid and gas side stop valves completely.
WARNING
Note that valve A must be closed!
2
Turn on the power of the outdoor unit and indoor units.
NOTICE
When an indoor unit is connected to the refrigerant
system and the indoor unit is turned off, automatic
charging will fail.
3
Make sure that the led on the PCB (A1P and A2P) on the
outdoor unit are as shown in the table below. This indicates that
the system is operating normally.
H1P H2P H3P H4P H5P H6P H7P
Led state
Throughout the manual the state of the leds is indicated as
follows:
OFF
ON
blinking
ON or OFF
If H2P is lit up, check the type of error based on the error code in
the remote controller and correct the error in accordance with
"12.4. Test operation" on page 19.
4
Automatically charge the refrigerant according to the procedure
described below.
DANGER: RISK OF ELECTROCUTION
Do not touch anything else than the push-buttons (BS1~5)
on the PCB (A2P) when making the settings. These
settings must be done with the power ON.
4.1 Press BS4 TEST once.
H1P H2P H3P H4P H5P H6P H7P
RXYSQ6P8Y1B9
VRVIII-S System air conditioner
4P357505-1 – 2013.08