Daikin RXYSQ6P8Y1B9 Installation Manual page 17

Vrviii-s system air conditioner
Table of Contents

Advertisement

4.2 Press BS4 TEST for 5 seconds. The unit will start running.
H1P H2P H3P H4P H5P H6P H7P
If the led display below appears, the automatic refrigerant
charging restriction has been exceeded. Additional refrigerant
must be charged by calculating the additional refrigerant
charging amount.
H1P H2P H3P H4P H5P H6P H7P
or
H1P H2P H3P H4P H5P H6P H7P
If the led display below appears, check the indoor unit
connection capacity.
H1P H2P H3P H4P H5P H6P H7P
If the led display below appears, the liquid and gas side stop
valves may be closed.
H1P H2P H3P H4P H5P H6P H7P
NOTICE
If you want to repeat the automatic refrigerant charging
operation from step 4.2, fully open the liquid and gas side
stop valves and press the BS1 MODE button once.
4.3 When the led indication becomes as shown in the table below in
about 15 to 30 minutes after start of operation, open valve A at
once to start charging of the refrigerant.
Immediately after starting charging of the refrigerant by opening
valve A, press BS4 TEST once. When BS4 TEST is not pressed
within 10 minutes after the led indication is shown, charging is
stopped.
H1P H2P H3P H4P H5P H6P H7P
4.4 The led indication becomes as shown in the table below during
automatic refrigerant charging.
During automatic refrigerant charging, the remote controller
indicates TEST (test operation) and
H1P H2P H3P H4P H5P H6P H7P
NOTICE
If the led display below appears, the refrigerant tank is
empty. Replace the refrigerant tank, open valve A and
re-charge.
H1P H2P H3P H4P H5P H6P H7P
The led indication becomes as shown in the table below when
automatic refrigerant charging is about to end. Prepare to close
the valve on the refrigerant tank.
H1P H2P H3P H4P H5P H6P H7P
RXYSQ6P8Y1B9
VRVIII-S System air conditioner
4P357505-1 – 2013.08
4.5 When the led indication becomes as shown in the table below,
Description of error
Inappropriate outdoor
temperature
Description of error
Inappropriate indoor
temperature
Description of error
Inappropriate indoor unit
connection capacity
Description of error
Stop valve is closed
Code on remote controller
PA
(external control).
5
Code on remote
controller
6
PA
Code on remote controller
PE
NOTICE
It is possible that the code PE is not shown on the
remote controller but this does not indicate a
malfunction. The led indication can immediately shift
to the situation as shown in "Case 1: Charging
complete" on page 13.
quickly close valve A and follow instructions as described below.
CAUTION
When adding refrigerant is done or when
pausing, close the valve on the refrigerant tank
immediately.
More refrigerant might be charged by any
remaining pressure after the machine is stopped.
The outdoor fan may keep rotating a little bit
more, but this does not indicate a malfunction.
Case 1: Charging complete
H1P H2P H3P H4P H5P H6P H7P
Charging of the refrigerant is complete. Press BS1 MODE
button once and go to step 5.
Case 2: Recharging operation
H1P H2P H3P H4P H5P H6P H7P
Press BS1 MODE button once and perform automatic
refrigerant charging again starting from Step 4.2.
Case 3: Charging interrupted
H1P H2P H3P H4P H5P H6P H7P
Something is preventing normal operation:
 Is the gas side stop valve completely open?
 Are the valve on the refrigerant tank and valve A open?
Check if the BS4 TEST button was pressed within 10
minutes after the valves were opened.
 Is the indoor unit air intake vent or outlet vent blocked?
After correcting the problem, press BS1 MODE button once and
perform automatic refrigerant charging again starting from
step 4.2.
Case 4: Failure
H1P H2P H3P H4P H5P H6P H7P
(a) An error in the system interrupted the operation of the unit. Check the
error by using the error code displayed on the remote controller. For an
explanation of the error codes, see "Error codes on the remote controller"
on page 20 and solve the problem.
After correcting the problem, press BS1 MODE button once and
perform automatic refrigerant charging again starting from
step 4.2.
When charging is complete, determine the weight of refrigerant
that was added and fill in the amount in the "Additional
refrigerant charge label" attached to service precautions plate on
the unit.
After adding the refrigerant, do not forget to close the lid of the
service port. The tightening torque for the lid is 11.5~13.9 N•m.
Code on remote controller
P9
Code on remote controller
P8
Code on remote controller
P2
Error code on remote
controller
(a)
See footnote
Installation manual
13