Performing calibration via PROFIBUS PA

To use PROFIBUS PA, you will need a PC configuration tool: we recommend SIMATIC
PDM. Please consult the operating instructions or online help for details on using
SIMATIC PDM. (An Application Guide
SIMATIC PDM
is available on our website: www.siemens.com/processautomation.)
Changing parameter settings
First launch SIMATIC PDM, connect to SITRANS LR 200, and upload data from the
device.
Adjust parameter values in the parameter view field (right side of screen).
After adjusting the value, press Enter (the status fields read Changed).
When you have completed the adjustments, open the Device menu, download data
to the device, and save parameter settings offline (the status fields go blank).
Calibration
Only four settings are required for a Quick Setup:
High Calibration Point and High Level Point
Low Calibration Point and Low Level Point
1
2
3
,
,
.
High Level Point
(default: 100%)
Low Level Point
(default: 0%)
Far Range
1.
The point to which all of the above parameters are referenced. For the standard rod
antenna, please see
configurations, please see
onwards.
2.
The value produced by the echo processing, representing the distance from the
Sensor Reference Point to the target.
3.
Level Value: the level measured in level units.
Page 22
SITRANS LR 200 (PROFIBUS PA) – INSTRUCTION MANUAL
SMPI PROFIBUS PA instruments and
2
Sensor Value
3
Level
Level Offset
Secondary Value 1
SITRANS LR 200 Dimensions
Appendix D: Flange Adapter Versions
Sensor Reference Point
Sensor Offset
High
Calibration
Point
Low Calibration
Point
on page 13. For other
, from page 44
1
7ML19985HP01