76J Pneumatic Fulscope Recorder
MAINTENANCE
4.5.2
Thermal System
1. Turn off all electrical power to Fulscope.
2. Remove chart plate and connecting link.
3. Remove terminal block mounting screws and necessary wires to move terminal block for
access to case opening. Refer to Figure 17.
4. Remove upper screws in access plate.
5. If capillary is behind chart motor remove motor.
6. Remove measuring element base screws Figure 17.
Figure 17. Removing System from Case
27