Local Operation Pad (Lop) - Danfoss FCM305 56 Instruction Manual

Vlt drivemotor fcm 300 series
Table of Contents

Advertisement

Remote Mounting Kit continued....

Local Operation Pad (LOP)

The LOP is wired directly to the X101 control
terminals. The LOP provides speed control, a start/
stop function and, depending on how it is wired and
programmed, the following three functions:
1. Dual speed operation
2. Dual mode operation (Uses 2-Set-up Menus)
3. Dual direction operation (For forward or reverse)
NOTE!
After wiring the LOP, cut off or isolate any
excess wire.
Function/settings
Function/settings
Function/settings
Function/settings
Function/settings
Default - Dual speed operation
Default - Dual speed operation
Default - Dual speed operation
Default - Dual speed operation
Default - Dual speed operation
(connect orange wire):
(connect orange wire):
(connect orange wire):
(connect orange wire):
(connect orange wire):
No changes to factory setting.
Function 2 - Dual mode operation
Function 2 - Dual mode operation
Function 2 - Dual mode operation
Function 2 - Dual mode operation
Function 2 - Dual mode operation
(connect orange wire):
(connect orange wire):
(connect orange wire):
(connect orange wire):
(connect orange wire):
Select desired modes of operation
in Setups 1 and 2 (use para. 4-6)
Parameter 335 = 18 (select Setup)
Function 3 - Dual direction operation
Function 3 - Dual direction operation
Function 3 - Dual direction operation
Function 3 - Dual direction operation
Function 3 - Dual direction operation
(connect grey wire):
(connect grey wire):
(connect grey wire):
(connect grey wire):
(connect grey wire):
Parameter 335 = 10 (start reversing)
Parameter 200 = 1 (both directions)
*If no reset is required,
do not connect the brown wire
7-4
FCM 300 Series
At power up the unit will always be in stop mode.
Set reference will be stored during power down. If
permanent start mode is desired, connect terminal
6 to terminal 4 and do not connect orange/gray
wire to terminal 4. This means the stop function on
LOP is disabled.
W W W W W iring
iring
iring
iring
iring
Color of wire
Color of wire
Color of wire
Color of wire
Color of wire
White
Brown
Orange or Gray
Green
Red
Yellow
Blue
Key
Key
(Start)
(Start)
Key
Key
(Start)
(Start)
Key
Key
Key
(Start)
(Start)
(Start) Key
Key
Key
(Start)
(Start)
(Start)
Run on set
Run on
reference
10 Hz**
(+/-)
jog speed
Run with
Run with
Setup 1
Setup 2
Run
Run
forward
reverse
**or set parameter 213
T T T T T erminal
erminal
erminal
erminal
erminal
Function
Function
Function
Function
Function
2
Reference
3
Reset
4
See table under button
5
See table under button
6
+24V
7
+10V
8
Ground
Key
Key
(Stop)
(Stop)
Key
Key
Key
(Stop)
(Stop)
(Stop)
Stop (and
reset* - if trip)
Stop (and
reset* - if trip)
Stop (and
reset* - if trip)
MG.03.B6.2G - VLT is a registered Danfoss trademark