" " Actual operation hour meter clear (Pr. 171)

4.2.42 Actual operation hour meter clear (Pr. 171)
Pr. 171 "actual operation hour meter
clear"
You can clear the monitor (actual operation hour) value which is selected when Pr. 52
is "23".
Parameter
Number
171
<Setting>
Write "0" in the parameter to clear the actual operation hour.
Pr. 173 to Pr. 176 &

4.2.43 Input terminal function selection (Pr. 180 to Pr. 183)

" Input terminal function selection (Pr. 180 to Pr. 183)
Pr. 180 "RL terminal function selection"
Pr. 181 "RM terminal function selection"
Pr. 182 "RH terminal function selection"
Pr. 183 "MRS terminal function selection"
Use these parameters to select/change the input terminal functions.
Parameter
Terminal
Number
180
181
182
183
Factory
Setting
Setting
Range
0
0
& Refer to Pr. 160.
& &
Factory
Symbol
Setting
RL
0
RM
1
RH
2
MRS
6
Related parameter
Pr. 52 "control panel/PU main
display data selection"
Factory-Set Terminal
Function
Low-speed operation
command (RL)
Middle-speed operation
command (RM)
High-speed operation
command (RH)
Output shut-off (MRS)
148
PARAMETERS
Setting
Range
0 to 8, 16, 18
0 to 8, 16, 18
0 to 8, 16, 18
0 to 8, 16, 18