Monitoring Reference (Pr. 55, Pr. 56) - Mitsubishi Electric FR-E 500 Instruction Manual

Hide thumbs Also See for FR-E 500:
Table of Contents

Advertisement

" " Monitoring reference (Pr. 55, Pr. 56)

4.2.21 Monitoring reference (Pr. 55, Pr. 56)
Pr. 55 "frequency monitoring reference"
Pr. 56 "current monitoring reference"
Set the frequency or current which is referenced when the output frequency or output
current is selected for the AM terminal.
Parameter
Factory
Number
Setting
55
Rated output
56
current
<Setting>
Refer to the above diagrams and set the frequency monitoring reference value in
Pr. 55 and the current monitoring reference value in Pr. 56.
Pr. 55 is set when Pr. 158 = 0 and Pr. 56 is set when Pr. 158 = 1.
In Pr. 55 and Pr. 56, set the frequency and current at which the output voltage of
terminal AM will be 10V.
Note: The maximum output voltage of terminal AM is 10VDC.
Setting
Range
50Hz
0 to 400Hz
0 to 500A
10VDC (terminal AM)
Output frequency
Pr.55
Related parameters
Pr. 158 "AM terminal function
selection"
Pr. 901 "AM terminal calibration"
10VDC (terminal AM)
Output current
91
PARAMETERS
Pr.56
4

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e 520s ecFr-e 540 ec

Table of Contents