2 SYSTEM CONFIGURATION

2.5 Precautions when Configuring the System

CPU module
Q12PRHCPU, Q25PRHCPU
Q12PHCPU, Q25PHCPU
Q02CPU, Q02HCPU, Q06HCPU,
Q12HCPU, Q25HCPU
1
Q00JCPU, Q00CPU, Q01CPU
Master module
Remote I/O module
2 - 12
Take the following points into consideration when configuring a remote I/O net system.
(1)
Remote I/O networks and PLC to PLC networks cannot be mixed on the same
MELSECNET/H network. Always configure separate networks.
(2)
Only MELSECNET/H network modules can be connected to a MELSECNET/H
remote I/O network. They cannot be mixed with MELSECNET/10 network
modules.
(3)
In combinations of remote I/O and PLC-to-PLC networks, up to 4
MELSECNET/H network systems can be configured per CPU module
(Q02CPU/Q02HCPU/Q06HCPU/Q12HCPU/Q25HCPU/Q12PHCPU/Q25PHCPU
/Q12PRHCPU/Q25PRHCPU).
(4)
The following CPU modules and network modules are applicable to the remote
master station.
Max. No. of applicable network
modules
4 (including PLC-to-PLC networks)
4 (including PLC-to-PLC networks)
4 (including PLC-to-PLC networks)
Not mountable
1 : Use a CPU module with the first 5 digits of the serial No. 02092 or later.
Network module
QJ71LP21
QJ71LP21-25
QJ71LP21S-25
QJ71LP21G
QJ71BR11
QJ72LP25-25
QJ72LP25G
QJ72BR15
2 : When using a master module as a multiplexed remote master or sub-master
station, the first 5 digits of the serial No. must be 04012 or later.
Function
Multiplexed remote
Multiplexed remote
I/O network for
I/O network
redundant system
Available
N/A
Available
N/A
N/A
Applicable function version
Multiplexed remote I/O network
for redundant system
Function version D or later
MELSEC-Q
Remote I/O network
N/A
N/A
Available
N/A
Available
N/A
N/A
Multiplexed remote I/O network
2 or remote I/O network
Function version B or later