Wire size for control and relay terminals
Use wires within the specifications listed below. For safe wiring and reliability, it is recommended
to use ferrules, but if solid or stranded wire is used, stripping length should be 8mm.
Relay output terminal
Control logic
terminal
Relay terminal
Recommended ferrule
For safe wiring and reliability, it is recommended to use following ferrules.
Wire size
Model name of
2
mm
(AWG)
0.25 (24)
AI 0.25-8YE
0.34 (22)
AI 0.34-8TQ
0.5 (20)
AI 0.5-8WH
0.75 (18)
AI 0.75-8GY
* Supplier: Phoenix contact
Crimping pliers: CRIPMFOX UD 6-4 or CRIMPFOX ZA 3
How to connect?
(1) Push down the orange actuating lever by a slotted screwdriver (width 2.5mm max.).
(2) Insert the conductor.
(3) Pull out the screwdriver then the conductor is fixed.
2.5mm
Solid
2
mm
(AWG)
0.2 to 1.5
(AWG 24 to 16)
0.2 to 1.5
(AWG 24 to 16)
L [mm]
ferrule *
12.5
12.5
14
14
Stranded
2
mm
(AWG)
0.2 to 1.0
(AWG 24 to 17)
0.2 to 1.0
(AWG 24 to 17)
Φd [mm]
0.8
0.8
1.1
1.3
Push down the
orange actuating
lever.
18
Control logic terminal
8mm
Ferrule
2
mm
(AWG)
0.25 to 0.75
(AWG 24 to 18)
0.25 to 0.75
(AWG 24 to 18)
Φ d
ΦD [mm]
2.0
2.0
2.5
2.8
Insert in the
Pull out the
conductor.
screwdriver to fix
the conductor.
8
L
Φ D