Installing; Emc-Compliant Setup Of The Machine Or Plant - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converters chassis devices with cu240b-2 and cu240e-2
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Installing

4.1

EMC-compliant setup of the machine or plant

The inverter is designed for operation in industrial environments where strong electromagnetic
fields are to be expected.
Reliable and disturbance-free operation is only guaranteed for EMC-compliant installation.
To achieve this, subdivide the control cabinet and the machine or system into EMC zones:
EMC zones
Figure 4-1
Inside the control cabinet
● Zone A: Line supply connection
● Zone B: Power electronics
Devices in Zone B generate energy-rich electromagnetic fields.
● Zone C: Control and sensors
Devices in Zone C do not generate any energy-rich electromagnetic fields themselves, but
their functions can be impaired by electromagnetic fields.
Outside the control cabinet
● Zone D: Motors, braking resistors
Devices in Zone D generate electromagnetic fields with a significant amount of energy
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2017, FW V4.7 SP6, A5E34259001B AD
Example of the EMC zones of a plant or machine
4
51