5.2.3
Setting the frequency by analog input (voltage input/current input)
POINT
 Switch ON the STF(STR) signal to give a start command.
 Use the potentiometer (frequency setting potentiometer) (voltage input) or 4-to-20mA input (current input) to
give a frequency command.
[Connection example for voltage input]
(The inverter supplies 5V power to the frequency setting
potentiometer. (terminal 10))
Forward rotation start
Reverse rotation start
Frequency setting
potentiometer
Operation example
Operate at 60Hz.
Screen at power-ON
1.
The monitor display appears.
Assignment of the AU signal (current input) (Refer to the step 3 for voltage input.)
Set Pr. 160 to "0" to activate extended parameters.
2.
To assign the AU signal, set "4" in one of Pr. 178 to Pr. 184. (Refer to page 5 to change the setting.)
Turn ON the AU signal.
Start
3.
Turn the start switch (STF or STR) ON.
[RUN] blinks fast because the frequency command is not given.
Acceleration  constant speed
For voltage input, turn the potentiometer (frequency setting potentiometer) clockwise slowly to full.
4.
For current input, input 20mA.
The frequency value on the display increases in Pr. 7 Acceleration time, and "
[RUN] indicator is lit during forward rotation operation and blinks slowly during reverse rotation operation.
Deceleration
For voltage input, turn the potentiometer (frequency setting potentiometer) counterclockwise slowly to full.
5.
For current input, input 4mA.
The frequency value on the display decreases in Pr. 8 Deceleration time, and the motor stops rotating with "
[RUN] blinks fast.
Stop
6.
Turn the start switch (STF or STR) OFF.
[RUN] turns OFF.
REMARKS
 For voltage input, the frequency (maximum potentiometer setting) at the full right turn of the (frequency setting) potentiometer is
60Hz in the initial setting. (To change the setting, use Pr.125.) (Refer to page 31.)
 To input 10VDC to the terminal 2, set Pr. 73 Analog input selection = "0". The initial value is "1 (0 to 5V input)" (
4 of the FR-E700 Instruction Manual (Applied).).
 For current input, the frequency at 20mA input is 60Hz in the initial setting. (To change the setting, use Pr. 126.) (
Chapter 4 of the FR-E700 Instruction Manual (Applied).)
 To always select the External operation mode, set Pr. 79 Operation mode selection = "2 (External operation mode)".
Start and stop using terminals (External operation)
[Connection example for current input]
Assign the AU signal in one of Pr. 178 to Pr. 184.
Inverter
STF
STR
SD
10
2
5
Operation
Forward rotation start
Reverse rotation start
AU signal
Current signal
source
(4 to 20mADC)
" (60.00Hz) appears.
Inverter
STF
STR
AU signal (terminal RH)
SD
4(+)
5(-)
" (0.00Hz) displayed.
Refer to Chapter
Refer to
30
5