(2) Total wiring length
The overall wiring length for connection of a single motor or multiple motors should be within the value in the table below.
Cable
Pr. 72 Setting
Type
(carrier frequency)
1 (1kHz) or lower
Unshielded
cable
2 (2kHz) or higher
1 (1kHz) or lower
Shielded
cable
2 (2kHz) or higher
When driving a 400V class motor by the inverter, surge voltages attributable to the wiring constants may occur at the
motor terminals, deteriorating the insulation of the motor. Take the following measures 1) or 2) in this case.
1) Use a "400V class inverter-driven insulation-enhanced motor" and set frequency in Pr. 72 PWM frequency selection
according to wiring length.
Carrier frequency
2) Connect the surge voltage suppression filter (FR-ASF-H/FR-BMF-H) on the inverter output side.
NOTE
 Especially for long-distance wiring, the inverter may be affected by a charging current caused by the stray
capacitances of the wiring, leading to a malfunction of the overcurrent protective function, fast response current limit
function, or stall prevention function or a malfunction or fault of the equipment connected on the inverter output side.
If malfunction of fast-response current limit function occurs, disable this function. If malfunction of stall prevention
function occurs, increase the stall level. (
operation selection in Chapter 4 of the FR-E700 Instruction Manual (Applied))
 When using the automatic restart after instantaneous power failure function with the wiring length exceeding 100m,
select without frequency search (Pr. 162 = "1, 11"). (
Voltage
0.1K
0.2K
Class
200V class
200m
200m
400V class
-
-
200V class
30m
100m
400V class
-
-
200V class
50m
50m
400V class
-
-
200V class
10m
25m
400V class
-
-
Wiring Length
50m or less
50m to 100m
14.5kHz or less
8kHz or less
Refer to Pr. 22 Stall prevention operation level and Pr. 156 Stall prevention
0.4K
0.75K
1.5K
300m
500m
500m
200m
200m
300m
200m
300m
500m
30m
100m
200m
75m
100m
100m
50m
50m
75m
50m
75m
100m
10m
25m
50m
Exceeding 100m
2kHz or less
Refer to Chapter 4 of the FR-E700 Instruction Manual (Applied))
Wiring
3.7K
2.2K
or Higher
500m
500m
500m
500m
500m
500m
300m
500m
100m
100m
100m
100m
100m
100m
75m
100m