3. GENERAL SPECIFICATION

3. GENERAL SPECIFICATION
Item
Operation ambient
temperature
Storage ambient
temperature
Operation ambient
humidity
Storage ambient
humidity
Conforms to the JIS
Vibration durability
B 3502 and IEC
Shock durability
Operation
ambiance
Operation height *3
Installation area
Over-voltage
category *1
Pollution level *2
*1 Indicates the location the device is connected, from the public cable network to the device structure wiring
*2 This is an index which indicates the degree of conductive object generation in the environment where the
*3 Do not use or store the PC in the environment where the pressure is higher than the atmospheric pressure
The general specification common to various modules is shown.
Table 3.1 General specification
When there is intermittent vibration
Frequency
10 to 57Hz
57 to 150Hz
When there is continuous vibration
61131-2
Frequency
10 to 57Hz
57 to 150Hz
Conforms to the JIS B 3502 and IEC 61131-2 (147 m/s
.
area
Category II applies to the devices to which the power is supplied from a fixed equipment.
Surge withstand voltage for devices with up to 300V of rated voltage is 2500V.
device is used. Pollution level 2 is when only non-conductive pollution occurs. A temporary conductivity
caused by condensation must be expected occasionally.
at sea level. Otherwise, malfunction may result. To use the PC in high-pressure environment, contact your
nearest Mitsubishi representative.
Specification
0 to 55°C
-20 to 75°C
10 to 90%RH, no condensation
10 to 90%RH, no condensation
Acceleration
2
9.8m/s
Acceleration
2
4.9m/s
2
), 3 times each in 3 directions)
No corrosive gas
2000m(6562 ft.) or less
On the control panel
II or less
2 or less
3 - 1
MELSEC-A
Amplitude
Sweep count
0.075mm
10 times each in
(0.003 in.)
X, Y, and Z
directions
Amplitude
Sweep count
0.035mm
(0.001 in.)