Applied Control And Functions; Applied Control For Indoor Unit; Control Specifications - Toshiba MMY-MAP0806HT8(J)P Service Manual

Hide thumbs Also See for MMY-MAP0806HT8(J)P:
Table of Contents

Advertisement

6.

Applied control and Functions

6-1. Applied Control for Indoor Unit

6-1-1. Control Specifications

NO.
Item
Upon power
supply reset
1
Operation
selection
2
Room temp.
control
3
Automatic
capacity control
4
AMP Air Conditioning
1. Identification of outdoor unit
When the power supply is reset, the outdoor unit is identified, and control is
redirected according to the identification result.
2. Indoor fan speed and air flow direction control availability settings
Settings such as indoor fan speed and air flow direction control availability are
replaced on the basis of EEPROM data.
3. If power supply reset is performed in the wake of a fault, the check code is cleared.
If the abnormality persists after the Start/Stop button on the remote controller is
pressed to resume operation, the check code is redisplayed on the remote
controller.
1. The operation mode changes in response to an operation selection command
issued via the remote controller.
Remote controller command
STOP
FAN
COOL
DRY
HEAT
1. Adjustment range - remote controller temperature setting (°C)
COOL/DRY
Wired type
18~29
Wireless type
18~30
2. In heating operation, the temperature setting may be fine-tuned via the DN code
"06".
SET DATA
Temperature setting adjustment
Factory default
SET DATA
2
1. The outdoor unit determines the operational capacities of indoor units according
to the difference between Ta and Ts.
Ta
Cooling
(°C)
+2
SD
SB
+1
S9
S7
Ts
S5
S3
-1
Specification outline
Control outline
Air conditioner shutdown
Fan operation
Cooling operation
Drying operation
Heating operation
HEAT
18~29
16~30
0
2
+0°C
+2°C
Ta
Heating
(°C)
+1
S0
S3
S5
Ts
S7
S9
-1
SB
SD
-2
S0
SF
− 76 −
www.ampair.co.uk | sales@ampair.co.uk
Ts: Temperature
setting
Ta: Room temperature
Shift in heating suction
temperature
(not applicable to
remote controller
thermo operation)
4
6
+4°C
+6°C
Ts: Temperature
setting
Ta: Room temperature
Remarks