Siemens Simatic S7-1500 Manual page 21

Digital output module dq 8x230vac/2a st triac
Hide thumbs Also See for Simatic S7-1500:
Table of Contents

Advertisement

Output current
For signal "1" rated value
For signal "1" permitted range, min.
For signal "1" permitted range, max.
For signal "0" residual current, max.
Output delay with resistive load
"0" to "1", max.
"1" to "0", max.
Parallel connection of two outputs
For logic operations
For increased performance
For redundant control of a load
Switching frequency
With resistive load, max.
With inductive load, max.
With lamp load, max.
Total current of outputs
Current per channel, max.
Current per group, max.
Current per module, max.
Triac outputs
Size of motor starter according to NEMA, max.
Cable length
shielded, max.
unshielded, max.
Isochronous mode
Isochronous mode (application synchronized up to
terminal)
Interrupts/diagnostics/status information
Diagnostics function
Substitute values can be applied
Interrupts
Diagnostic interrupt
Diagnostics alarms
Monitoring of supply voltage
Wire break
Short-circuit
Diagnostics indicator LED
RUN LED
ERROR LED
Monitoring of supply voltage (PWR LED)
Channel status display
For channel diagnostics
For module diagnostics
Digital output module DQ 8x230VAC/2A ST Triac (6ES7522-5FF00-0AB0)
Manual, 09/2016, A5E03485733-AD
Technical specifications
6ES7522-5FF00-0AB0
2 A
10 mA
15 A; max. 1 AC cycle
2 mA
1 AC cycle
1 AC cycle
No
No
Yes
10 Hz
0.5 Hz
1 Hz
2 A; see additional description in the manual
2 A; see additional description in the manual
10 A; see additional description in the manual
5
1000 m
600 m
No
No
Yes
No
No
No
No
Yes; green LED
Yes; red LED
No
Yes; green LED
No
Yes; red LED
21

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-1500

Table of Contents