Read Coils (Command Code: 0X01) - Mitsubishi FX3U Series User Manual

Hide thumbs Also See for FX3U Series:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3U
User's Manual - MODBUS Serial Communication Edition
7.4

Read Coils (Command Code: 0x01)

Reads the status (ON/OFF) of one or more coils.
1) Request message format (Master → Slave)
2) Response message format (Slave → Master)
(When completed normally)
Function code
(When completed with an error)
*1. Exception and error codes are stored in special data registers and special auxiliary relays in the case
of error completion. Refer to Chapter 6 for storage location, confirmation methods, and other detailed
contents.
50
Function code
Head coil number
Function
(0000
to FFFF
code
H
(01
)
H
(H)
Function
Number of
Device data
code
read bytes
(01
)
n
H
(Device data 1 to n)
Device data 1
Device data n
The read coil statuses are stored in order from low-order to high-order bits.
When the number of read points is not a multiple of 8, the excess bits turn to 0.
Function code
Function code
Data
Read points
)
(0001
H
H
(L)
(H)
Data
Device data
1
(Number of read bytes n)
b7
b6
b5
b4
b3
Data
Exception
(81
)
code*
1
H
7 MODBUS Standard Commands
7.4 Read Coils (Command Code: 0x01)
to 07D0
)
H
(L)
n
b2
b1
b0
Bit device
storage order
0 : OFF
1 : ON

Hide quick links: