3. SELECTING INSTALLATION SITE

Please attach additional thermal insulation material to the unit body when it is believed that the relative
humidity in the ceiling exceeds 80%. Use glass wool, polyethylene foam, or similar with a thickness of 10
mm or more as thermal insulation material.
For this unit, you are able to select air flow direction.
To enable the discharge of air in 2 or 3 directions, it is necessary to purchase the sealing member of air dis-
charge outlet.
(1) Select an installation site where the following conditions are fulfilled and that meets your cus-
tomer's approval.
• In the upper space (including the back of the ceiling) of the indoor unit where there is no possible drip-
ping of water from the refrigerant pipe, drain pipe, water pipe, etc.
• Where optimum air distribution can be ensured.
• Where nothing blocks air passage.
• Where condensate can be properly drained.
• Where the ceiling is strong enough to bear the indoor unit weight.
• Where the false ceiling is not noticeably on an incline.
• Where sufficient clearance for maintenance and service can be ensured.
• Where there is no risk of flammable gas leakage.
• Where piping between indoor and outdoor units is possible within the allowable limit.
(Refer to the installation manual for the outdoor unit.)
>
*
NOTE
• Leave 200 mm or more space where marked with the *, on sides where the air outlet is closed.
Model
·
·
·
FFQ25
35
50
60
CAUTION
• Install the indoor and outdoor units, power cord and connecting wires at least 1 meter away from televi-
sions or radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter may not be sufficient enough to eliminate the
noise.)
(2) Air flow direction
Select the air flow directions best suited to the room and point of installation. (For air outlet in 2 or 3 direc-
tions, it is necessary to make field settings by remote controller and to close the air outlet(s). Refer to the
installation manual of the sealing member of air discharge outlet and the section entitled 10. FIELD SET-
TING)
English
[Space required for installation] (mm)
Air
Air
outlet
outlet
Air
inlet
>
*
1500
1500
Fig. 1
285 (Confirm the space of 295 or more)
>
*
1500
>
*
1500
>
*
1500
>
*
Fig. 2
H
1500
5