Connection of wiring between units, ground wire and for the remote control cord (Refer to Fig. 29)
• Wiring between units and ground wire
Remove the control box lid and connect wires of matching number to the power supply terminal block
(4P)inside. And connect the ground wire to the terminal block. In doing this, pull the wires inside through
the hole and fix the wires securely with the included clamp (4).
• Give enough slack to the wires between the clamp (4) and power supply terminal block. (Use Fig. 30 as a
guide and allow at least 80mm for removing the sheath.)
• Remove the control box lid and pull the wires inside through the hole and connect to the terminal block for
remote controller (6P). (no polarity) Securely fix the remote controller cord with the included clamp (4).
• Give enough slack to the wires between the clamp (4) and the terminal block for the remote controller.
• After connection, attach sealing material (12)
• Be sure to attach it to prevent the infiltration of water from the outside.
Wiring Remote controller cord
Note
(attached)
Clamp(4)
(Big)
(attached)
Clamp(4)
(Small)
Clamp
material
Wiring between units
Note
Wiring between
units
Clamp(4)
(Big)
(attached)
Clamp
material
16
Remote controller cord
Ground the shield part of shielded wire.
(
Refer to Note 2 in "8. WIRING EXAMPLE"
After clamping
Clamp(4)(small)
to wire sheath,
clamp the wire
sheath with
Clamp(4)(Big)
to clamp
material.
Be sure to clamp
wire sheath.
After securing the
clamp (4) to clamp
material, cut off
any extra material
10~15mm
Power supply
terminal block
Be sure to clamp
wire sheath.
After securing the
clamp (4) to clamp material,
cut off any extra material
Fig. 29
)
Terminal block for
remote controller (6P)
control box lid
Wiring diagram label
(Back side of control box lid)
Remove the
control box lid
(take off 2
screws)
Outdoor
Indoor
unit
unit
Note)
Be sure to attach it to prevent the infiltration of water
from the outside.
(attached)
Sealing material (12)
Attach completely to
hole of wiring without
leaving any space
Wiring
(Inside)
(Outside)
[How to attach sealing materials]
(Wiring between units)
How to connect power
supply terminal block
(4P) with ground wire
Sealing
material(12)
(attached)
Wiring to
outside
English