Adding refrigerant

After finishing vacuuming, exchange the vacuum pump with a refrigerant canister and start additional charging of
refrigerant.
Calculation of additional refrigerant charge amount
Refrigerant charge amount at shipment from the factory does not include the refrigerant for pipes at the local site.
For refrigerant to be charged in pipes at the local site, calculate the amount and charge it additionally.
NOTE
If the additional refrigerant amount indicates minus as the result of calculation, use the air conditioner without
additional refrigerant.
Outdoor unit type
MAP080
Charging amount (kg)
Additional refrigerant
=
Real length of liquid pipe
charge amount at local site
Table 1
Liquid pipe dia. (mm)
Additional refrigerant amount / 1 m
liquid pipe (kg/m)
43-EN
AMP Air Conditioning
MAP100
MAP120
MAP140
MAP160
MAP180
11.0
Corrective amount of
Additional refrigerant
refrigerant depending on HP
×
×
+
charge amount per 1 m
1.3
of co-operating outdoor units
liquid pipe (Table 1)
6.4
9.5
12.7
15.9
19.1
0.025
0.055
0.105
0.160
0.250
Table 2
Equivalent
HP
8HP
10HP
12HP
14HP
16HP
18HP
20HP
22HP
MAP200
24HP
26HP
28HP
30HP
32HP
(Table 2)
34HP
36HP
38HP
22.2
40HP
42HP
0.350
Charging of refrigerant
• Keeping the valve of the outdoor unit closed, be sure to charge the liquid refrigerant into the service port at the
liquid side.
• If the specified amount of refrigerant cannot be charged, fully open the valves of the outdoor unit at liquid and
gas sides, operate the air conditioner in COOL mode, and then charge refrigerant into service port at the gas
side. In this time, choke the refrigerant slightly by operating the valve of the canister to charge liquid refrigerant.
• The liquid refrigerant may be charged suddenly, therefore be sure to charge refrigerant gradually.
2
2
Combination of outdoor unit
Model name of
MMY-
outdoor unit
MMY-
Unit 1
Unit 2
MAP0806*
MAP0806*
-
MAP1006*
MAP1006*
-
MAP1206*
MAP1206*
-
MAP1406*
MAP1406*
-
MAP1606*
MAP1606*
-
MAP1806*
MAP1806*
-
MAP2006*
MAP2006*
-
AP2216*
MAP1206*
MAP1006*
AP2416*
MAP1406*
MAP1006*
AP2616*
MAP1406*
MAP1206*
AP2816*
MAP1406*
MAP1406*
AP3016*
MAP1606*
MAP1406*
AP3216*
MAP1806*
MAP1406*
AP3416*
MAP1806*
MAP1606*
AP3616*
MAP1806*
MAP1806*
AP3816*
MAP2006*
MAP1806*
AP4016*
MAP2006*
MAP2006*
AP4216*
MAP1406*
MAP1406*
www.ampair.co.uk | sales@ampair.co.uk
Corrective of
refrigerant
(kg)
Unit 3
-
2
-
3
-
8
-
10
-
12
-
14
-
15
-
6
-
8
-
12
-
12
-
14
-
15
-
16
-
18
-
22
-
24
MAP1406*
14
44-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents