5.7 INPUTS/OUTPUTS
!"
PATH: SETTINGS
INPUTS/OUTPUTS
# VIRTUAL INPUT
#
There are 32 virtual inputs that can be individually programmed to respond to input signals from the keypad (Commands
menu) and communications protocols. All virtual input operands are defaulted to OFF = 0 unless the appropriate input sig-
nal is received. Virtual input states are preserved through a control power loss.
If the
VIRTUAL INPUT x FUNCTION
the input. If set to "Enabled", the input operates as shown on the logic diagram and generates output FlexLogic™ operands
in response to received input signals and the applied settings.
There are two types of operation: Self-Reset and Latched. If
transits from OFF = 0 to ON = 1, the output operand will be set to ON = 1 for only one evaluation of the FlexLogic™ equa-
tions and then return to OFF = 0. If set to "Latched", the virtual input sets the state of the output operand to the same state
as the most recent received input, ON =1 or OFF = 0.
5
The "Self-Reset" operating mode generates the output operand for a single evaluation of the FlexLogic™
equations. If the operand is to be used anywhere other than internally in a FlexLogic™ equation, it will
NOTE
likely have to be lengthened in time. A FlexLogic™ timer with a delayed reset can perform this function.
SETTING
VIRTUAL INPUT 1
FUNCTION:
Disabled=0
Enabled=1
"Virtual Input 1 to ON = 1"
"Virtual Input 1 to OFF = 0"
SETTING
VIRTUAL INPUT 1
TYPE:
Latched
Self - Reset
5-166
!"

VIRTUAL INPUTS

1
VIRTUAL INPUT
FUNCTION: Disabled
VIRTUAL INPUT
MESSAGE
Virt Ip 1
VIRTUAL INPUT
MESSAGE
TYPE: Latched
VIRTUAL INPUT
MESSAGE
EVENTS: Disabled
is to "Disabled", the input will be forced to 'Off' (Logic 0) regardless of any attempt to alter
AND
AND
AND
Figure 5–107: VIRTUAL INPUTS SCHEME LOGIC
G60 Generator Management Relay
!
VIRTUAL INPUT 1(32)
Range: Disabled, Enabled
1
Range: Up to 12 alphanumeric characters
1 ID:
Range: Self-Reset, Latched
1
Range: Disabled, Enabled
1
is "Self-Reset", when the input signal
VIRTUAL INPUT x TYPE
S
Latch
R
5 SETTINGS
5.7.2 VIRTUAL INPUTS
SETTING
VIRTUAL INPUT 1 ID:
(Flexlogic Operand)
OR
Virt Ip 1
827080A2.CDR
GE Multilin