5.6 CONTROL ELEMENTS
!"
PATH: SETTINGS
CONTROL ELEMENTS
# DIGITAL ELEMENT 1
#
5
There are 16 identical Digital Elements available, numbered 1 to 16. A digital element can monitor any FlexLogic™ oper-
and and present a target message and/or enable events recording depending on the output operand state. The digital ele-
ment settings include a 'name' which will be referenced in any target message, a blocking input from any selected
FlexLogic™ operand, and a timer for pickup and reset delays for the output operand.
DIGITAL ELEMENT 1 INPUT: Selects a FlexLogic™ operand to be monitored by the digital element.
DIGITAL ELEMENT 1 PICKUP DELAY: Sets the time delay to pickup. If a pickup delay is not required, set to "0".
DIGITAL ELEMENT 1 RESET DELAY: Sets the time delay to reset. If a reset delay is not required, set to "0".
DIGITAL ELEMENT 1 PICKUP LED: This setting enables or disabled the digital element pickup LED. When set to
"Disabled", the operation of the pickup LED is blocked.
SETTING
DIGITAL ELEMENT 01
FUNCTION:
Disabled = 0
Enabled = 1
SETTING
DIGITAL ELEMENT 01
INPUT:
Off = 0
SETTING
DIGITAL ELEMENT 01
BLOCK:
Off = 0
CIRCUIT MONITORING APPLICATIONS:
Some versions of the digital input modules include an active Voltage Monitor circuit connected across Form-A contacts.
The voltage monitor circuit limits the trickle current through the output circuit (see technical specifications for Form-A).
5-158
!"

DIGITAL ELEMENTS

DIGITAL ELEMENT
FUNCTION: Disabled
DIG ELEM
MESSAGE
Dig Element 1
DIG ELEM
MESSAGE
Off
DIG ELEM
MESSAGE
DELAY:
DIG ELEMENT
MESSAGE
PICKUP LED: Enabled
DIG ELEM
MESSAGE
DELAY:
DIG ELEM
MESSAGE
Off
DIGITAL ELEMENT
MESSAGE
TARGET: Self-reset
DIGITAL ELEMENT
MESSAGE
EVENTS: Disabled
SETTING
DIGITAL ELEMENT 01
NAME:
AND
RUN
Figure 5–101: DIGITAL ELEMENT SCHEME LOGIC
G60 Generator Management Relay
!
DIGITAL ELEMENT 1(16)
Range: Disabled, Enabled
1
Range: 16 alphanumeric characters
1 NAME:
Range: FlexLogic™ operand
1 INPUT:
Range: 0.000 to 999999.999 s in steps of 0.001
1 PICKUP
0.000 s
Range: Disabled, Enabled
1
Range: 0.000 to 999999.999 s in steps of 0.001
1 RESET
0.000 s
Range: FlexLogic™ operand
1 BLOCK:
Range: Self-reset, Latched, Disabled
1
Range: Disabled, Enabled
1
SETTINGS
DIGITAL ELEMENT 01
PICKUP DELAY:
DIGITAL ELEMENT 01
RESET DELAY:
t
PKP
INPUT = 1
t
RST
5 SETTINGS
5.6.8 DIGITAL ELEMENTS
FLEXLOGIC OPERANDS
DIG ELEM 01 DPO
DIG ELEM 01 PKP
DIG ELEM 01 OP
827042A1.VSD