13  Directory of the Parameters in Installer Mode and Expert Mode

13.2.3 External/Backup (230#)

231# General
No.
Name
231.01 PvFeedTmStr Start time for PV grid feed-in
231.02 PvFeedTmStp Stop time for PV grid feed-in
231.03 ExtLkTm
231.06 ExtSrc
231.14 AC2NSel
232# Grid Control
No.
Name
232.01 Country
232.02 GdVtgMin
232.03 GdVtgMax
100
SI60H-80H-BE-en-20
Description
in hh:mm:ss (expert mode)
in hh:mm:ss (expert mode)
Lock time after reverse
power or relay protection
in minutes (expert mode)
Generator and grid
operating mode
Terminal at which the neutral
conductor is connected to
AC2.
Description
Country data set
(protected by
SMA Grid Guard)
Minimum line voltage
in V (expert mode,
protected by
SMA Grid Guard)
Maximum line voltage
in V (expert mode,
protected by
SMA Grid Guard)
Value
Explanation
00:00:00
to
23:59:59
00:00:00
to
23:59:59
0 min to
60 min
PvOnly
Only AC sources in the
stand-alone grid, no generator
in the off-grid system
Gen
Generator
Grid
Utility grid
GenGrid
Generator or utility grid
N
The neutral conductor is
connected to terminal N.
NTT
The neutral conductor is
connected to terminal N
Value
Explanation
Other
Individual setting
VDE-AR-4105
Code of Practice
VDE-AR-N 4105
AS4777
Standard AS4777
172.50 V to
230 V / 50 Hz
210.01 InvVtgNom
220 V / 60 Hz
210.01 InvVtgNom
230 V / 50 Hz
to 264.50 V
220 V / 60 Hz
SMA Solar Technology AG
Default
value
04:00:00
22:00:00
20 min
.
TT
Default
value
184.00 V
194.00 V
264.50 V
242.00 V
Operating Manual