6. The thermostat will automatically power on.
Step 7 — SET THERMOSTAT
CONFIGURATION
When power is first applied, AC will appear for 5 seconds to
indicate that the thermostat setup as an air conditioner (AC), the
most common application. You may need to make an adjustment to
this setting depending on the system you've connected. See
explanation under Option 01- Equipment Type below.
To adjust the default configuration, you will need to enter
Configuration Mode. A description of each configurable option is
listed below.
To Enter The Configuration Mode:
1. Press and hold the FAN key for about 10 seconds until the
display changes so that only two pairs of digits are showing.
2. The configuration number, now 01, will appear in the set-
point/temperature location and the configuration setting will
appear in the clock location.
3. The configuration number (left pair) will be flashing which
4. To cause the opposite pair to flash (to be adjustable), press
the MODE key.
5. Successive presses of the MODE key alternate between the
configuration number (left) and the configuration setting
(right).
6. To exit the configuration mode, press the HOLD/END key.
7. If no key is pressed for 3 minutes, the configuration mode
will automatically exit, returning the thermostat to normal
operation.
Option 01 - Equipment type
You may need to make an adjustment to this setting depending on
the system you've connected. If you're unsure about your system
type, refer to wiring diagrams beginning on page 5.
Options: Air Conditioner (AC), Heat Pump (HP), PH, or PC
Description:
1. AC or PC controls 1 speed air conditioner with one stage of
heat.
2. HP or PH controls 1 speed heat pump with 1 stage of auxil-
iary heat.
3. PH or PC selects PTAC units (Packaged Terminal Air Con-
ditioners) which are used in motel rooms and other rented
spaces. When this option is selected, the display shows only
the setpoint, not the room temperature. Also, the compres-
sor timeguard is disabled, allowing the compressor to turn
on immediately when a demand is established.
Option 03 - Fahrenheit/Centigrade
A150229
Default: Fahrenheit (F)
Selections: Fahrenheit (F), Centigrade (C)
Description: This selection operates the thermostat in either
Fahrenheit or Centigrade.
Option 04 - G (fan) ON with W (Heat) Selection
Default: G not energized with W (OF)
Options: G not energized with W (OF), G energized with W (ON)
Description: This selection determines whether the fan (G) is to be
ON or OFF when W (furnace or strip heat) is ON. Furnaces and
fan coils which manage their own blowers do not require a separate
G signal. Some auxiliary heaters require a separate G signal to
operate the blower when W is applied.
Option 10 - Reversing valve
Default: Reversing valve energized in cooling (C)
Options: Reversing valve energized in cooling (C), Reversing
valve energized in heating (H)
Description: Applies only when configured for Heat Pump
applications. Most systems use the orange (O) wire and are
A150230
energized in cooling.
S Select Energized in Cooling (C) if you connected an (O) wire in
the O/B terminal to activate the reversing valve output when
there is a call for cooling.
S Select Energized in Heating (H) if you connected a (B) wire in
the O/B terminal to activate the reversing valve output when
there is a call for heating.
S If you are unsure, consult your heating and cooling system
A150231
equipment installation instructions or contact Carrier customer
support.
Option 13 - Room Air Temperature Offset
Default: 0°F
Options: +/- 5°F or +/- 3°C.
Description: The number of degrees to be added to the displayed
A150232
temperature to calibrate the measured room temperature. The
selected number is the number of degrees, plus or minus, which
will be added to actual temperature. This option is in °F even if
Option 03 is set for °C.
Option 15 - Auto Changeover
Default: Off (OF)
Options: On (ON), Off (OF)
Description: This feature allows the thermostat to automatically
change between heating and cooling mode when a demand has
A150233
been present in the opposite mode for a period of 20 minutes.
Manually changing either the cooling or the heating setpoint will
allow an auto changeover to occur without the 20 minute time
constraint. The heat setpoint and cool setpoint are separated by a
minimum of 2°F.
Option 21 - Keypad Lockout
Default: Off (OF)
Options: On (ON), Off (OF)
Description: With ON selected the keypad will be locked and can
be unlocked by simultaneously pressing the UP and DOWN keys
4