Ntp-G7 Install The Power And Ground - Cisco ONS 15454 DWDM Installation And Operation Manual

Hide thumbs Also See for ONS 15454 DWDM:
Table of Contents

Advertisement

DLP- G14 Remove the Backplane Sheet Metal Cover

NTP-G7 Install the Power and Ground

Purpose
Tools/Equipment
Prerequisite Procedures (ETSI)
Required/As Needed
Onsite/Remote
Security Level
Warning
Shut off the power from the power source or turn off the breakers before beginning work.
This equipment is intended to be grounded. Ensure that the host is connected to earth ground during
Warning
normal use.
Warning
Do not mix conductors of dissimilar metals in a terminal or splicing connector where physical contact
occurs (such as copper and aluminum, or copper and copper-clad aluminum), unless the device is
suited for the purpose and conditions of use.
Cisco ONS 15454 DWDM Installation and Operations Guide, R4.7
1-30
This procedure installs power feeds and grounds the ONS 15454.
#2 Phillips screwdriver
Medium slot-head screwdriver
Small slot-head screwdriver
Screws
(ETSI only.) Power cable (from fuse panel to MIC-A/P and to MIC-C/T/P),
shipped with the ONS 15454 ETSI
(ANSI only.) Power cable (from fuse and alarm panel to assembly), #10
AWG, copper conductors, 194 degrees F [90 degrees C])
Ground cable 13.3-mm² (#6 AWG) stranded
(ETSI only.) Two-hole grounding lug, shipped with the ONS 15454 ETSI
Listed pressure terminal connectors such as ring and fork types; connectors
must be suitable for 5.26-mm² (#10 AWG) copper conductors
(ANSI only.) Wire wrapper
Wire cutters
Wire strippers
Crimp tool
Fuse panel
NTP-G4 Open and Remove the FMEC Cover (ETSI Only), page
1-23
(ETSI)
NTP-G6 Install the MIC-A/P and MIC-T/C/P FMECs (ETSI Only),
page 1-27
(ANSI)
NTP-G5 Remove the Backplane Covers (ANSI Only), page 1-26
Required
Onsite
None
Chapter 1
Install the Shelf and Common Control Cards
September 2004