Preparation For Use, Storage Or Shipping; Preparation For Use - Hobart 60CU24 Operation And Maintenance Manual With Illustrated Parts List

60 kva, 3 phase, 115/200 volt, 400 hz. generator set series 500060c
Table of Contents

Advertisement

OM-2098C / Operation and Maintenance Manual
60CU24 / Series 500060C / 400 Hz. Generator Set
Section 2
Preparation for Use, Storage, or Shipping

1) Preparation for Use

a) Inspection/Check
Inspect the unit thoroughly prior to operation.
(1) Remove blocking, banding, ties, and other securing material.
(2) Inspect exterior for shipping damage such as broken lights, damaged sheet metal, etc.
(3) Open all canopy doors and inspect interior for foreign material such as rags, tools, shipping
papers, etc.
(4) Check fuel, coolant, oil hoses and connections for visible leaks. Visually inspect the compartment
floor and ground surface under the unit for signs of leakage. If leaks are found, correct by
tightening hose clamps, tube fitting, etc., as required.
(5) Check security of generator set retaining components.
(6) Check the following for sufficient quantity:
a
Fuel
Press "LAMPS" push-button button to energize fuel gage when engine is stopped. Fuel is
supplied from a customer-furnished source.
NOTE: For recommended fuel specifications refer to the Engine Manufacturers Operation and
Maintenance Manual provided with this manual.
b
Engine coolant
Remove radiator cap to check coolant level. Coolant level should be at the bottom of the filler
neck.
CAUTION
BE SURE the cooling system antifreeze solution is adequate to protect below the
lowest temperature expected.
NOTE: For antifreeze protection, use a solution of 50% permanent antifreeze (Ethylene glycol) and
50% clean water.
Lubricating oil capacity (w/ filter)
Coolant capacity system
April 01, 2005
ENGINE OIL AND COOLANT CAPACITIES
10 quarts (9.5 liters)
38 quarts (36 liters)
Figure 1
Chapter 1-2
Page 1