5.3 SYSTEM SETUP
This configuration could be used on a two winding transformer, with one winding connected into a breaker-and-a-half sys-
tem. The following figure shows the arrangement of Sources used to provide the functions required in this application, and
the CT/VT inputs that are used to provide the data.
5
!"
PATH: SETTINGS
SYSTEM SETUP

# LINE

#
These settings specify the characteristics of the line. The line impedance value should be entered as secondary ohms.
This data is used for fault location calculations. See the
the Source and Trigger for fault calculations.
5-28
F 1
DSP Bank
F 5
Source 3
U 1
Volts Amps
V
V
Volts
M 1
Source 4
M 1
M 5
Figure 5–4: EXAMPLE USE OF SOURCES
!"
LINE
POS SEQ IMPEDANCE
MAGNITUDE:
POS SEQ IMPEDANCE
MESSAGE
ANGLE: 75°
ZERO SEQ IMPEDANCE
MESSAGE
MAGNITUDE:
ZERO SEQ IMPEDANCE
MESSAGE
ANGLE: 75°
LINE LENGTH UNITS:
MESSAGE
km
LINE LENGTH (km
MESSAGE
100.0
C60 Breaker Management Relay
Source 1
Amps
51BF-1
A
W
Var
A
W
Var
Amps
Range: 0.01 to 250.00
3.00 Ω
Range: 25 to 90° in steps of 1
Range: 0.01 to 650.00
9.00 Ω
Range: 25 to 90° in steps of 1°
Range: km, miles
Range: 0.0 to 2000.0 in steps of 0.1
):
!
SETTINGS
PRODUCT SETUP
5 SETTINGS
Source 2
Amps
51BF-2
87T
51P
UR Relay
827794A1.CDR
5.3.4 LINE
in steps of 0.01
in steps of 0.01
!"
menu for assigning
FAULT REPORT