Display Properties; Communications - GE C60 Instruction Manual

Multilin breaker management relay ur series
Hide thumbs Also See for C60:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
!
PATH: SETTINGS
PRODUCT SETUP
# DISPLAY
# PROPERTIES
Some relay messaging characteristics can be modified to suit different situations using the display properties settings.
Flash messages are status, warning, error, or information messages displayed for several seconds in response to certain
key presses during setting programming. These messages override any normal messages. The time a flash message
remains on the display can be changed to accommodate different reading rates. If no keys are pressed for a period of time,
the relay automatically displays a default message. This time can be modified to ensure messages remain on the screen
long enough during programming or reading of actual values.
To extend the life of the phosphor in the vacuum fluorescent display, the brightness can be attenuated when displaying
default messages. When interacting with the display using the keypad, the display always operates at full brightness.
a) SERIAL PORTS
5
!
PATH: SETTINGS
PRODUCT SETUP

# COMMUNICATIONS

#
# SERIAL PORTS
#
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The C60 is equipped with up to 3 independent serial communication ports. The faceplate RS232 port is intended for local
use and has fixed parameters of 19200 baud and no parity. The rear COM1 port type will depend on the CPU ordered: it
may be either an Ethernet or an RS485 port. The rear COM2 port is RS485. The RS485 ports have settings for baud rate
and parity. It is important that these parameters agree with the settings used on the computer or other equipment that is
connected to these ports. Any of these ports may be connected to a personal computer running URPC. This software is
used for downloading or uploading setting files, viewing measured parameters, and upgrading the relay firmware to the lat-
est version. A maximum of 32 relays can be daisy-chained and connected to a DCS, PLC or PC using the RS485 ports.
For each RS485 port, the minimum time before the port will transmit after receiving data from a host can be
set. This feature allows operation with hosts which hold the RS485 transmitter active for some time after
each transmission.
NOTE
5-8
!"

DISPLAY PROPERTIES

FLASH MESSAGE
TIME:
1.0 s
DEFAULT MESSAGE
MESSAGE
TIMEOUT: 300 s
DEFAULT MESSAGE
MESSAGE
INTENSITY: 25 %
!"
COMMUNICATIONS
RS485 COM1 BAUD
RATE: 19200
RS485 COM1 PARITY:
None
RS485 COM1 RESPONSE
MIN TIME:
0 ms
RS485 COM2 BAUD
RATE: 19200
RS485 COM2 PARITY:
None
RS485 COM2 RESPONSE
MIN TIME:
0 ms
C60 Breaker Management Relay
Range: 0.5 to 10.0 s in steps of 0.1
Range: 10 to 900 s in steps of 1
Range: 25%, 50%, 75%, 100%
!
SERIAL PORTS
Range: 300, 1200, 2400, 4800, 9600, 14400, 19200, 28800, 33600,
38400, 57600, 115200. Only active if CPU 9A is ordered.
Range: None, Odd, Even
Only active if CPU Type 9A is ordered
Range: 0 to 1000 ms in steps of 10
Only active if CPU Type 9A is ordered
Range: 300, 1200, 2400, 4800, 9600, 14400, 19200, 28800, 33600,
38400, 57600, 115200
Range: None, Odd, Even
Range: 0 to 1000 ms in steps of 10
5 SETTINGS
5.2.2 DISPLAY PROPERTIES
5.2.3 COMMUNICATIONS