GE C60 Instruction Manual page 238

Multilin breaker management relay ur series
Hide thumbs Also See for C60:
Table of Contents

Advertisement

B.3 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 10 of 29)
ADDR
REGISTER NAME
40E2
IEC 60870-5-104 Protocol Common Addr of ASDU
40E3
IEC 60870-5-104 Protocol Cyclic Data Tx Period
40E4
IEC No. of Sources used in M_ME_NC_1 point list
40E5
IEC Current Default Threshold
40E6
IEC Voltage Default Threshold
B
40E7
IEC Power Default Threshold
40E8
IEC Energy Default Threshold
40E9
IEC Other Default Threshold
40EA
IEC Communications Reserved (22 items)
4100
DNP Binary Input Block of 16 Points (58 items)
Data Logger Commands (Read/Write Command)
4170
Clear Data Logger
Data Logger (Read/Write Setting)
4180
Data Logger Rate
4181
Data Logger Channel Settings (16 items)
Clock (Read/Write Command)
41A0
RTC Set Time
Clock (Read/Write Setting)
41A2
SR Date Format
41A4
SR Time Format
41A6
IRIG-B Signal Type
Fault Report Settings and Commands (Read/Write Setting)
41B0
Fault Report Source
41B1
Fault Report Trigger
Fault Report Settings and Commands (Read/Write Command)
41B2
Fault Reports Clear Data Command
Oscillography (Read/Write Setting)
41C0
Oscillography Number of Records
41C1
Oscillography Trigger Mode
41C2
Oscillography Trigger Position
41C3
Oscillography Trigger Source
41C4
Oscillography AC Input Waveforms
41D0
Oscillography Analog Channel X (16 items)
4200
Oscillography Digital Channel X (63 items)
Trip and Alarm LEDs (Read/Write Setting)
4260
Trip LED Input FlexLogic Operand
4261
Alarm LED Input FlexLogic Operand
User Programmable LEDs (Read/Write Setting) (48 modules)
4280
FlexLogic Operand to Activate LED
4281
User LED type (latched or self-resetting)
4282
...Repeated for module number 2
4284
...Repeated for module number 3
4286
...Repeated for module number 4
4288
...Repeated for module number 5
428A
...Repeated for module number 6
428C
...Repeated for module number 7
428E
...Repeated for module number 8
4290
...Repeated for module number 9
4292
...Repeated for module number 10
4294
...Repeated for module number 11
4296
...Repeated for module number 12
4298
...Repeated for module number 13
429A
...Repeated for module number 14
429C
...Repeated for module number 15
B-18
RANGE
0 to 65535
1 to 65535
1 to 6
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 1
0 to 58
0 to 1
0 to 7
---
0 to 235959
0 to 4294967295
0 to 4294967295
0 to 2
0 to 5
0 to 65535
0 to 1
1 to 64
0 to 1
0 to 100
0 to 65535
0 to 4
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 1
C60 Breaker Management Relay
APPENDIX B
UNITS
STEP
FORMAT
---
1
F001
s
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F197
---
1
F126
---
1
F178
---
---
F600
---
1
F003
---
1
F051
---
1
F052
---
1
F114
---
1
F167
---
1
F300
---
1
F126
---
1
F001
---
1
F118
0 (Auto Overwrite)
%
1
F001
---
1
F300
---
1
F183
2 (16 samples/cycle)
---
1
F600
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F127
DEFAULT
0
60
1
30000
30000
30000
30000
30000
0
0 (Not Used)
0 (No)
1 (1 min)
0
0
0
0
0 (None)
0 (SRC 1)
0
0 (No)
15
50
0
0
0
0
0
0
1 (Self-Reset)
GE Multilin

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents