Procedures During Operation; Stopping Operation - Shindaiwa DG25MK Owner's And Operator's Manual

Diesel engine generator
Hide thumbs Also See for DG25MK:
Table of Contents

Advertisement

< Note >
Change the Frequency Selector Switch if the frequency in the area where using this
generator changes.
(Refer to "5-2.Meters,Throttle Lever,(3)Freqency Slector Switch")
Adjust the voltage regulator dial to the specified voltage.
8
50Hz Operation
60Hz Operation
* The values in brackets are for when set to 200/220V.
Turn the breaker to ON to start AC power delivery.
9

9-2. Procedures during Operation

(1) Checks after Startup
Make sure that all meters and indicators are in normal status. (Refer to section "5. Equipment".)
Check that there is no abnormal vibration or noise.
Check that the exhaust gas color is normal. When operation is normal, the exhaust gas should
be colorless or slightly bluish.
< Note >
If abnormal, stop using this generator and request authorized distributor where the generator was
purchased to repair the generator.
(2) Adjustment during Operation
During load operation, check the voltmeter and finely adjust voltage using the voltage
regulator dial.
Bleeding air from the fuel system when the engine stops due to running out of fuel
This generator is equipped with an automatic air bleeding mechanism. Perform the
following procedures when the engine stops due to running out of fuel to easily bleed
the air from the system.
Add fuel to the generator.
1
Turn the starter switch to RUN. Air bleeding is completed approximately in 30 sec.
2
< Note >
Turn the throttle switch to IDLING, start the engine and check that the air is completely bled from
the system. If air bleeding is not complete, engine rotation will not be stable. In that case, repeat
the air bleeding operation.

9-3. Stopping Operation

CAUTION : BURNS
Do not touch the engine and surrounding components immediately after
stopping the engine as they are still hot.
400V [200V]
440V [220V]
25