Load Connections; Load Cable Selection - Shindaiwa DG25MK Owner's And Operator's Manual

Diesel engine generator
Hide thumbs Also See for DG25MK:
Table of Contents

Advertisement

If installing this generator, set up barriers or fencing completely around the boundary
line of the construction area and take measures to prevent persons not involved in the
construction from entering the area.
Always set the generator on a hard, flat and leveled surface that serves as the
foundation.
Keep the generator 1 m or more from walls or other hindrances so that the operation
panel door and left/right check doors are accessible for internal inspection/maintenance.
< Note >
This equipment must be operated on hard and flat surface. Operating under any other
conditions may result in malfunctions.
Do not block the airflow from radiator vent or muffler exhaust. It may result in reduced engine
performance, overheating, or damage to the electrical parts.
Operating in dusty area or salty air (by the ocean), or any other particulate environment may
result in clogged radiator, which may cause overheating, other malfunctions and insulation
deterioration. Use extreme care, frequent checks and maintenance.
7.

Load Connections

7-1. Load Cable Selection

CAUTION : PROPERTY DAMAGE
Cable burnout can occur due to generated heat if the load current exceeds
the allowable current of the cable.
The voltage drop between cables is large if the cable is excessively long or
thin, resulting in decreased input voltage to equipment using the generator,
thereby causing decreased performance, faulty operation and malfunction.
Select cable for use that has sufficient thickness and an allowable current possible for use,
giving consideration to the distance from the generator to the equipment using the
generator.
< Note >
Select cable with a thickness that ensures that the voltage drop across the cable will be within 5%
of the rated voltage.
Load Cable Selection Tables
(Ex.) If used voltage is 440V and voltage drops by 22 V.
Length
100 ft (30 m)
or less
Current
20 A
12
25 A
12
30 A
12
35 A
12
40 A
12
Length
50 m
or less
Current
20 A
3.5
25 A
3.5
30 A
3.5
35 A
3.5
40 A
3.5
3-phase: Cabtyre cables
200 ft
300 ft
(61 m)
(91 m)
12
12
12
12
12
12
12
12
12
12
75 m
100 m
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
16
400 ft
500 ft
(122 m)
(152 m)
12
12
12
12
12
10
10
10
10
10
125 m
150 m
3.5
3.5
3.5
3.5
3.5
5.5
5.5
5.5
5.5
5.5
(Unit: AWG)
600 ft
(183 m)
12
10
10
8
8
2
(Unit: mm
)
200 m
3.5
5.5
5.5
8
8