Compressor Lock - Daikin F-Series Service Manual

Inverter multi for 2 rooms
Hide thumbs Also See for F-Series:
Table of Contents

Advertisement

SiBE12-712
4.9

Compressor Lock

E6
Remote
Controller
Display
Method of
Judging from current waveform generated when high-frequency voltage is applied to the
Malfunction
compressor.
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Note:
If the model doesn't have SPM, replace the outdoor unit PCB.
Service Diagnosis
The system will be shut down if the error occurs 16 times.
Clearing condition: Continuous run for about 11 minutes (normal)
Compressor locked
Disconnection of compressor harness
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
(Precaution before turning on the power again)
Make sure the power has been off for at least 30 seconds.
Turn off the power. Disconnect the
harnesses U, V and W.
Check with the inverter checker (∗).
Normal?
YES
Turn off the power and reconnect
the harnesses. Turn on the power
again and get the system restarted.
Emergency stop
without compressor
running?
NO
System shut
down after errors repeated
several times?
YES
NO
YES
NO
Troubleshooting
∗ Inverter checker
Part No.: 1225477
Correct the power supply or
replace the SPM.
(Replace the outdoor unit
PCB.)
Replace the compressor.
Check the electronic
expansion valve.
Replace it as required.
Replace the compressor.
(R7031)