Jumper Settings

1.2.1 When Two Units are Installed in One Room
When two indoor units are installed in one room, the two wireless remote controllers can be set
for different addresses.
How to set the different addresses
(1) Remove the front panel.
(2) Remove the sensor parts cover (2-screws), then remove the electric parts box (1-screw).
(3) Slide the metallic cover to remove it. (4-claws on the electric parts box)
(4) Cut the jumper
(1) Slide the front cover and take it off.
(2) Cut the address jumper J4.
1.2.2
Jumper Setting
(On indoor control PCB)
Others
Control PCB of the indoor unit
JA
on PCB.
Wireless remote controller
J4
ADDRESS
EXIST
1
CUT
2
Jumper
Function
JC
Power failure
recovery function
JB
Fan speed setting
when compressor is
OFF on thermostat.
(effective only at
cooling operation)
J4
JA
ADDRESS
EXIST
1
CUT
2
(R4417)
When connected
(factory set)
Auto-restart
Unit does not resume operation
after recovering from a power
failure. Timer ON-OFF settings
are cleared.
Fan speed setting
;
Fan rpm is set to "0"
Remote controller
<Fan stop>
setting
Others
(R4418)
When cut