1-19. VARIOUS PROTECTIONS
1. DISCHARGE GAS TEMPERATURE OVERRISE PREVENTION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas
temperature.
When the discharge temperature becomes higher than Temperature ,the compressor frequency
is decreased 10rps, and it continues to decrease the frequency for 10rps every 120 seconds until
the temperature becomes lower than Temperature .
When the discharge temperature becomes lower than Temperature , the control of
the compressor frequency is released.
When the discharge temperature becomes higher than Temperature
and the indoor unit LED starts blinking.
(Table15 : Discharge Temperature Over Rise Prevention Control / Release Temperature)
Temperature
105°C
AMP Air Conditioning
Temperature
Temperature
100°C
115°C
www.ampair.co.uk | sales@ampair.co.uk
01-17
,the compressor is stopped