General Information

About these Installation Instructions

Take note of all symbols and notations intended to draw attention to potential hazards or important product
information. These include "WARNING", "CAUTION", and "IMPORTANT". See below.
WARNING
Indicates an imminently hazardous situation which,
if not avoided, could result in death, serious injury
or substantial product/property damage.
CAUTION
Indicates an imminently hazardous situation which,
if not avoided, may result in minor injury or product/
property damage.
IMPORTANT

Product Information

High efficiency gas-fired hot water condensing boiler.
For operation with modulating boiler water temperatures
in closed loop, forced circulation hot water heating
systems.
The Vitocrossal 300, CA3 boilers are CSA certified with
Viessmann burners which must be used in conjunction
with this boiler series.
The proper burner size must be verified and the burners
are factory adjusted so that the maximum input of the
appropriate boiler size is always observed. The gas burners
must always be installed according to the instructions
provided by the burner manufacturer.
The boiler model selected should be based on an accurate
heat loss calculation of the building. The boiler selected
must be compatible with the connected radiation.
10
Vitocrossal 300 CA3 Series 2.5 to 6.0 Installation/Service
Warnings draw your attention to the presence of
potential hazards or important product information.
 Cautions draw your attention to the presence of
potential hazards or important product information.
 Helpful hints for installation, operation or maintenance
which pertain to the product.
 This symbol indicates that additional, pertinent
information is to be found.
 This symbol indicates that other instructions must
be referenced.
The Vitocrossal 300, CA3 boiler is suitable for a maximum
operating pressure of 160 psig and a maximum boiler
water temperature of 210°F (99°C).
This boiler does not require a flow switch.
WARNING
Exposing the boiler to pressures and temperatures in
excess of those listed will result in damages, and will
render warranty null and void.