LG Multi V 5 Data Manual page 89

Hide thumbs Also See for Multi V 5:
Table of Contents

Advertisement

Outdoor
Combination
68/57
air temp.
(%)
TC
(°F DB)
MBh
-9.9
153.9
-5
153.9
0
153.9
5
153.9
10
153.9
14
153.9
20
153.9
25
153.9
30
153.9
35
153.9
40
153.9
45
153.9
50
153.9
55
153.9
50%
60
153.9
65
153.9
70
153.9
75
153.9
80
153.9
85
153.9
90
153.9
95
153.9
100
153.9
105
153.9
110
153.9
115
153.9
118
153.9
122
153.9
TC = Total Capacity (MBh).
PI = Power Input (kW) (includes compressor and outdoor fan).
Cooling range with the Low Ambient Baffle Kit (sold separately) is -9.9°F to +122°F and is achieved
only when all indoor units are operating in cooling mode. Does not impact heat recovery system
synchronous operating range.
The System Combination Ratio must be between 50–130%.
73/61
79/64
PI
TC
PI
TC
kW
MBh
kW
MBh
3.83
183.2
4.51
213.9
4.04
183.2
4.75
213.9
4.20
183.2
4.95
213.9
4.35
183.2
5.12
213.9
4.48
183.2
5.27
213.9
4.64
183.2
5.47
213.9
4.82
183.2
5.63
213.9
4.95
183.2
5.78
213.9
5.11
183.2
5.91
213.9
5.23
183.2
6.07
213.9
5.38
183.2
6.23
213.9
5.46
183.2
6.31
213.9
5.52
183.2
6.42
213.9
5.64
183.2
6.54
213.9
5.75
183.2
6.70
213.9
5.82
183.2
6.82
213.9
5.99
183.2
6.94
213.9
6.06
183.2
7.06
213.9
6.23
183.2
7.47
213.9
6.63
183.2
7.87
213.9
7.42
183.2
8.82
213.9
7.82
183.2
9.34
213.9
8.23
183.2
9.89
213.9
8.99
183.2
10.90
213.9
9.94
183.2
12.05
213.9
10.65
183.2
12.93
213.9
11.50
183.2
14.04
213.9
12.69
183.2
15.52
213.9
©
COOLING CAPACITY DATA
ARUM456BTE5 / ARUM456DTE5
456,000 Btu/h 208-230V / 460V Outdoor Units
Indoor Air Temp. °F DB/°F WB
80/67
85/70
PI
TC
PI
TC
kW
MBh
kW
MBh
5.04
228.0
5.43
242.4
5.31
228.0
5.74
242.4
5.54
228.0
5.95
242.4
5.74
228.0
6.18
242.4
5.90
228.0
6.35
242.4
6.11
228.0
6.59
242.4
6.38
228.0
6.83
242.4
6.58
228.0
7.02
242.4
6.79
228.0
7.22
242.4
6.95
228.0
7.42
242.4
7.14
228.0
7.59
242.4
7.23
228.0
7.70
242.4
7.35
228.0
7.82
242.4
7.47
228.0
7.94
242.4
7.70
228.0
8.23
242.4
7.82
228.0
8.35
242.4
7.99
228.0
8.58
242.4
8.18
228.0
8.70
242.4
8.77
228.0
9.46
242.4
9.29
228.0
10.06
242.4
10.46
228.0
11.29
242.4
11.05
242.4
228.0
12.00
11.70
228.0
12.70
242.4
12.94
228.0
14.01
242.4
14.34
228.0
15.57
242.4
15.41
228.0
16.76
242.4
16.75
228.0
18.23
242.4
18.52
228.0
20.23
242.4
Nominal capacity as rated: 0 ft. above sea level with 25 ft. of refrigerant piping.
0 ft. level difference between outdoor and indoor units.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and
67ºF wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
88/73
91/76
PI
TC
PI
TC
kW
MBh
kW
MBh
5.86
272.8
6.50
301.3
6.18
272.8
6.86
301.3
6.42
272.8
7.11
301.3
6.66
272.8
7.38
301.3
6.83
272.8
7.59
301.3
7.10
272.8
7.87
301.3
7.33
272.8
8.15
301.3
7.51
272.8
8.39
301.3
7.71
272.8
8.63
301.3
7.91
272.8
8.87
301.3
8.11
272.8
9.09
301.3
8.22
272.8
9.22
301.3
8.35
272.8
9.34
301.3
8.46
272.8
9.53
301.3
8.77
272.8
9.82
301.3
8.87
272.8
9.99
301.3
9.11
272.8
10.29
301.3
9.29
272.8
10.46
301.3
10.17
272.8
11.70
301.3
10.82
272.8
12.46
301.3
12.17
272.8
14.05
301.3
12.93
272.8
14.93
301.3
13.69
272.8
15.88
301.3
15.16
272.8
17.60
301.3
16.88
272.8
19.64
301.3
18.16
272.8
21.16
301.3
19.79
272.8
22.19
301.3
19.43
256.4
16.83
254.7
PERFORMANCE DATA | 89
PI
kW
7.19
7.59
7.90
8.18
8.42
8.73
9.06
9.34
9.62
9.86
10.11
10.26
10.41
10.58
11.01
11.17
11.53
11.77
13.34
14.24
16.12
17.12
18.16
20.20
22.58
24.34
25.02
19.00