LG Multi V 5 Data Manual page 144

Hide thumbs Also See for Multi V 5:
Table of Contents

Advertisement

HEATING CAPACITY DATA
ARUM408BTE5 / ARUM408DTE5
408,000 Btu/h 208-230V / 460V Outdoor Units
Outdoor air
Combination
temp.
(%)
TC
°F DB °F WB
MBh
-12.6
-13.0
309.4
-7.0
-7.6
332.5
-4.0
-4.4
346.3
0.0
-0.4
371.4
5.0
4.5
385.5
10.0
9.0
385.7
15.0
14.0
385.7
20.0
19.0
385.7
70%
25.0
23.0
385.7
30.0
28.0
385.7
35.0
32.0
385.7
40.0
36.0
385.7
45.0
41.0
385.7
47.0
43.0
385.7
50.0
46.0
385.7
55.0
51.0
385.7
60.0
56.0
385.7
-12.6
-13.0
285
-7.0
-7.6
307.7
-4.0
-4.4
328.1
0.0
-0.4
330.4
5.0
4.5
330.4
10.0
9.0
330.4
15.0
14.0
330.4
20.0
19.0
330.4
60%
25.0
23.0
330.4
30.0
28.0
330.4
35.0
32.0
330.4
40.0
36.0
330.4
45.0
41.0
330.4
47.0
43.0
330.4
50.0
46.0
330.4
55.0
51.0
330.4
60.0
56.0
330.4
-12.6
-13.0
276.3
-7.0
-7.6
276.3
-4.0
-4.4
276.3
0.0
-0.4
276.3
5.0
4.5
276.3
10.0
9.0
276.3
15.0
14.0
276.3
20.0
19.0
276.3
50%
25.0
23.0
276.3
30.0
28.0
276.3
35.0
32.0
276.3
40.0
36.0
276.3
45.0
41.0
276.3
47.0
43.0
276.3
50.0
46.0
276.3
55.0
51.0
276.3
60.0
56.0
276.3
TC = Total Capacity (MBh).
PI = Power Input (kW) (includes compressor and outdoor fan).
The System Combination Ratio must be between 50–130%.
Nominal capacity as rated: 0 ft. above sea level with 25 ft. of refrigerant piping.
0 ft. level difference between outdoor and indoor units.
144 | PERFORMANCE DATA
59
61
64
PI
TC
PI
TC
kW
MBh
kW
MBh
24.74
309.4
26.1
309.4
27.8
332.5
29.17
332.5
29.64
346.3
31.00
346.3
31.90
363.3
33.27
351.1
34.74
371.8
36.10
351.1
37.57
371.9
38.93
351.1
42.31
371.9
41.12
351.1
39.55
371.9
38.45
351.1
36.84
371.9
35.81
351.1
34.13
371.9
33.19
351.1
31.41
371.9
30.57
351.1
28.70
371.9
27.95
351.1
26.08
371.9
25.39
351.1
25.39
371.9
24.72
351.1
24.45
371.9
23.81
351.1
22.94
371.9
22.34
351.1
21.33
371.9
20.78
351.1
25.13
285
26.42
285
28.19
305.4
29.48
302
30.03
317.7
31.32
302.0
32.29
319.0
33.59
302.0
35.13
319.0
36.42
302.0
39.85
319.0
39.25
302.0
38.71
319.0
37.60
302.0
36.11
319.0
35.03
302.0
33.57
319.0
32.52
302.0
31.02
319.0
29.99
302.0
28.49
319.0
27.48
302.0
25.95
319.0
24.96
302.0
23.48
319.0
22.53
302.0
22.86
319.0
21.93
302.0
22.01
319.0
21.12
302.0
20.66
319.0
19.83
302.0
19.21
319.0
18.43
302.0
22.69
266.2
24.73
251.1
25.75
266.2
27.79
251.1
27.58
266.2
29.63
251.1
29.86
266.2
31.90
251.1
34.75
266.2
34.73
251.1
36.33
266.2
34.78
251.1
33.88
266.2
32.44
251.1
31.34
266.2
30.01
251.1
28.83
266.2
27.62
251.1
26.34
266.2
25.24
251.1
23.84
266.2
22.85
251.1
21.34
266.2
20.47
251.1
18.94
266.2
18.17
251.1
18.44
266.2
17.68
251.1
17.76
266.2
17.04
251.1
16.67
266.2
15.99
251.1
15.51
266.2
14.87
251.1
©
Indoor Air Temp. °F DB/°F WB
67
70
PI
TC
PI
TC
kW
MBh
kW
MBh
kW
28.14
308.5
30.33
307.5
32.5
31.21
325.8
33.59
319
35.98
33.04
332.6
35.55
319.0
38.05
35.31
335.1
37.96
319.0
40.62
38.15
335.1
39.31
319.0
40.49
40.97
335.1
39.61
319.0
38.23
39.34
335.1
37.68
319.0
36.02
36.79
335.1
35.25
319.0
33.71
34.29
335.1
32.87
319.0
31.45
31.79
335.1
30.50
319.0
29.20
29.30
335.1
28.12
319.0
26.94
26.80
335.1
25.74
319.0
24.68
24.38
335.1
23.43
319.0
22.49
23.73
335.1
22.81
319.0
21.89
22.85
335.1
21.97
319.0
21.09
21.45
335.1
20.62
319.0
19.79
19.95
335.1
19.18
319.0
18.41
28.36
279.4
30.9
273.7
33.44
31.42
287.9
34.02
273.7
36.63
33.26
287.9
35.86
273.7
38.46
35.53
287.9
37.21
273.7
38.88
38.36
287.9
37.53
273.7
36.71
38.37
287.9
36.45
273.7
34.52
35.94
287.9
34.16
273.7
32.39
33.41
287.9
31.79
273.7
30.16
30.93
287.9
29.45
273.7
27.99
28.45
287.9
27.13
273.7
25.80
25.97
287.9
24.79
273.7
23.63
23.50
287.9
22.47
273.7
21.44
21.10
287.9
20.22
273.7
19.33
20.54
287.9
19.68
273.7
18.82
19.78
287.9
18.95
273.7
18.13
18.56
287.9
17.79
273.7
17.01
17.27
287.9
16.54
273.7
15.83
27.79
239.7
30.39
228.4
30.85
239.7
32.44
228.4
34.01
32.69
239.7
34.27
228.4
35.85
34.95
239.7
34.74
228.4
34.52
34.69
239.7
33.55
228.4
32.40
32.48
239.7
31.38
228.4
30.29
30.29
239.7
29.26
228.4
28.21
28.03
239.7
27.04
228.4
26.06
25.82
239.7
24.88
228.4
23.95
23.59
239.7
22.71
228.4
21.83
21.37
239.7
20.54
228.4
19.72
19.14
239.7
18.37
228.4
17.60
17.01
239.7
16.29
228.4
15.57
16.56
239.7
15.86
228.4
15.16
15.96
239.7
15.27
228.4
14.59
14.97
239.7
14.33
228.4
13.70
13.92
239.7
13.34
228.4
12.74
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and
outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
73
76
PI
TC
PI
TC
PI
MBh
kW
MBh
kW
300.3
36.8
284.7
39.39
301.5
39.46
284.3
41.01
301.5
41.05
284.3
41.99
301.5
40.76
284.3
40.08
301.5
38.60
284.3
37.87
301.5
36.43
284.3
35.66
301.5
34.30
284.3
33.49
301.5
32.09
284.3
31.22
301.5
29.92
284.3
29.00
301.5
27.75
284.3
26.79
301.5
25.58
284.3
24.58
301.5
23.41
284.3
22.36
301.5
21.31
284.3
20.22
301.5
20.74
284.3
19.68
301.5
19.98
284.3
18.95
301.5
18.75
284.3
17.79
301.5
17.44
284.3
16.54
257.7
37.87
243.5
40.53
257.7
38.44
243.5
40.14
257.7
39.01
243.5
38.02
257.7
37.50
243.5
36.22
257.7
35.33
243.5
34.07
257.7
33.16
243.5
31.92
257.7
31.04
243.5
29.82
257.7
28.82
243.5
27.62
257.7
26.64
243.5
25.48
257.7
24.47
243.5
23.33
257.7
22.30
243.5
21.18
257.7
20.13
243.5
19.03
257.7
18.04
243.5
16.95
257.7
17.57
243.5
16.50
257.7
16.91
243.5
15.90
257.7
15.88
243.5
14.93
257.7
14.76
243.5
13.88
33
215
34.8
202.5
36.51
215
35.25
202.5
33.53
215.0
33.97
202.5
32.31
215.0
32.39
202.5
30.79
215.0
30.42
202.5
28.90
215.0
28.44
202.5
27.01
215.0
26.51
202.5
25.16
215.0
24.49
202.5
23.22
215.0
22.51
202.5
21.33
215.0
20.54
202.5
19.44
215.0
18.56
202.5
17.55
215.0
16.59
202.5
15.66
215.0
14.69
202.5
13.85
215.0
14.30
202.5
13.49
215.0
13.77
202.5
12.98
215.0
12.93
202.5
12.18
215.0
12.03
202.5
11.34
80
TC
Pl
MBh
kW
263.9
42.83
261.2
43.09
261.2
43.24
261.2
39.18
261.2
36.90
261.2
34.63
261.2
32.39
261.2
30.07
261.2
27.79
261.2
25.52
261.2
23.24
261.2
20.96
261.2
18.77
261.2
18.26
261.2
17.59
261.2
16.52
261.2
15.36
224.6
44.06
224.6
42.41
224.6
36.70
224.6
34.52
224.6
32.40
224.6
30.27
224.6
28.20
224.6
26.03
224.6
23.91
224.6
21.79
224.6
19.67
224.6
17.55
224.6
15.51
224.6
15.10
224.6
14.54
224.6
13.65
224.6
12.69
185.7
38.78
185.7
31.23
185.7
30.08
185.7
28.66
185.7
26.88
185.7
25.10
185.7
23.35
185.7
21.54
185.7
19.76
185.7
17.98
185.7
16.20
185.7
14.43
185.7
12.72
185.7
12.39
185.7
11.93
185.7
11.19
185.7
10.42