6. Replace the PCI adapter and make sure the PCI adapter is functioning normally.
• 80070201-0302ffff : Sensor [SensorElementName] has transitioned to critical from a less severe
state. (CPU 2 OverTemp)
This message is for the use case when an implementation has detected a Sensor transitioned to critical
from less severe.
May also be shown as 800702010302ffff or 0x800702010302ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Temperature
SNMP Trap ID
0
CIM Information
Prefix: PLAT ID: 0522
User Response
1. Make sure there is a node filler correctly installed for the empty node slot.
2. Make sure the air baffles are placed and correctly installed; and make sure the node cover
is installed and completely closed.
3. Make sure the fans are operating, and there are no obstructions to the airflow (both front and
rear of the server).
4. Reduce the Ambient temperature. The system must be operating within the specifications. (see
Features and specifications for more information)
5. Make sure the PCI adapter is supported by the server. To confirm, see the IBM ServerProven
website.
6. Replace the PCI adapter and make sure the PCI adapter is functioning normally.
• 80070201-1101ffff : Sensor [SensorElementName] has transitioned to critical from a less severe
state. (PCI 1 Temp)
This message is for the use case when an implementation has detected a Sensor transitioned to critical
from less severe.
May also be shown as 800702011101ffff or 0x800702011101ffff
Severity
Error
Appendix A. Integrated Management Module II (IMM2) error messages
277