Inspecting And Replacing Filters; Sealing The Unit - Lennox CBA27UHE-018 Installation Instructions Manual

Elite series air handler units
Hide thumbs Also See for CBA27UHE-018:
Table of Contents

Advertisement

ABOVE
FINISHED
SPACE?
NO
OVERFLOW
YES
NOTE — WHEN A AIR HANDLER IS LOCATED
ABOVE A FINISHED SPACE THE SECONDARY
DRAIN PAN MUST HAVE A LARGER FOOTPRINT
THAN THE AIR HANDLER.
SECONDARY
DRAIN PAN
WHEN A COIL IS LOCATED ABOVE A FINISHED SPACE, A
3/4" (19.1MM) SECONDARY DRAIN LINE MUST BE:
CONNECTED TO SECONDARY DRAIN PAN
OR
CONNECTED TO THE OVERFLOW DRAIN OUTLET OF
THE AIR HANDLER DRAIN PAN.
TRAPS MUST BE DEEP ENOUGH TO OFFSET MAXIMUM STATIC DIFFERENCES —
GENERALLY, TWO INCHES (51MM).
1
LENNOX P-TRAP 49P66 REQUIRES A LARGER INSTALLATION SPACE THAN THE J-TRAP 91P90.
2
PIPE NIPPLE PROVIDED IN BAG ASSEMBLY - SCH 80, 3/4" I. D. X 5" - 34K7401 (1): CUT THE PIPE IN HALF AND USE IT TO ROUTE THE MA IN DRAIN.

Inspecting and Replacing Filters

IMPORTANT
Filter access panel must be in place during unit operation.
Excessive warm air entering the unit may result in water
blow-off problems.
Filters may be duct-mounted or installed in the cabinet. A
filter is installed at the factory. Note that filter access door
fits over access panel. Air will leak if the access panel is
placed over the filter door.
Filters should be inspected monthly and must be cleaned
or replaced when dirty to assure proper air handler oper-
ation.
Reusable filters supplied with some units can be washed
with water and mild detergent. Some units are equipped
with standard throw-away type filters which should be re-
placed when dirty.
To replace filter:
1 - Loosen the thumbscrews holding the filter panel in
place. Remove the dirty filter.
2 - Insert new filter and replace panel.
OVERFLOW DRAIN LINE
ALWAYS RUN AN OVERFLOW DRAIN LINE. IF NOT POSSIBLE TO
ROUTE OVERFLOW DRAIN LINE, INSTALL LOW VOLTAGE
OVERFLOW
SWITCH
KIT.
WIRE
COMPRESSOR PER INSTRUCTIONS.
LENNOX #
X3169
COMPACT OVERFLOW SWITCH WITH 3/4" FEMALE SLIP INLET
AND MALE ADAPTER, TWO PART DESIGN FOR USE WHERE
OBSTRUCTIONS PREVENT DIRECT THREADING
AIR HANDLER DRAIN PAN
DRAIN
MAIN
DRAIN
FIGURE 8. Typical Main and Overflow Drain
KIT
TO
SHUT
DOWN
CLEAN OUT
PRESS IN
(DO NOT GLUE)
MAIN
DRAIN
CUT TO
REQUIRED
LENGTH
PROVIDED
2
PIPE NIPPLE
SIDE VIEW
FOR NEGATIVE PRESSURE COILS (BLOWER
AFTER COIL) TRAPS ARE REQUIRED ON ALL
DRAIN LINES CONNECTED TO COIL.
CBA27UHE
-018, -024, -030, -036
-042, -048, -060

Sealing the Unit

There must be an airtight seal between the bottom of
the air handler and the return air plenum. Use fiberglass
sealing strips, caulking, or equivalent sealing method
between the plenum and the air handler cabinet to
ensure a tight seal. Return air must not be drawn from a
room where this air handler or any gas-fueled appliance
(i.e., water heater), or carbon monoxide-producing
device (i.e., wood fireplace) is installed.
Seal the unit so that warm air is not allowed into the cabi-
net. Warm air introduces moisture, which results in water
blow-off problems. This is especially important when the
unit is installed in an unconditioned area.
Page 8
VENT MUST EXTEND
ABOVE HEIGHT OF
COIL DRAIN PAN BY
TWO INCHES (51MM)
VENT
1" X 3/4" X 3/4"
REDUCING
TEE WITH
PLUG
1
LENNOX
P-TRAP
49P66, J-TRAP #
91P90 OR ANY
PVC SCH 40 P- OR
J-TRAP 3/4"
2"
(51MM)
TRAP DEPTH
TABLE 3. Filter Dimensions
Filter Size – In. (mm)
20" x 20" (508mm x 508mm)
20" x 24" (508mm x 610mm)
WARNING
TO APPROVED
DRAIN
DRAIN LINE SHOULD
SLOPE A MINIMUM OF
ONE
INCH
PER
10
FEET (25MM PER 3
METERS)