System Performance With Advanced Microprocessor Controls; Temperature Control; Cooling/Heating Required, In Percent (%); Response To Control Types - Liebert Himod Operation & Maintenance Manual

Precision cooling for business-critical continuity
Hide thumbs Also See for Himod:
Table of Contents

Advertisement

4.0
S
P
YSTEM
ERFORMANCE WITH
This section provides details on how your Himod unit responds to user inputs and room conditions.
Refer to this section when you need specific information. This section includes details on control.
4.1

Temperature Control

4.1.1

Cooling/Heating Required, in Percent (%)

The temperature control program for the advanced microprocessor is based on a calculated % require-
ment for cooling/ heating.
4.1.2

Response to Control Types

Proportional Control
The % requirement is determined by the difference between the return air temperature and the tem-
perature setpoint. As the return air temperature rises above the temperature setpoint, the % cooling
required increases proportionally (from 0 to 100%) over a temperature band equal to the temperature
sensitivity plus 1 degree F. The % heating requirement is determined the same way as the tempera-
ture decreases below the setpoint. With this type of control the temperature at which the room is con-
trolled increases as the room cooling load increases. At full cooling load the room would be controlled
at a temperature equal to the setpoint plus the sensitivity.
4.1.3

Cooling Operation

One-Step Cooling, Compressorized Direct Expansion (DX) Systems
Cooling activates when the temperature control calculates a requirement for cooling of 100%. It is
deactivated when the cooling requirement drops below 50%. The hot gas bypass is energized on a call
for cooling.
To aid in lubricating the compressor, the hot gas bypass solenoid is delayed for 30 seconds on the initial
call for cooling and de-energized for 30 seconds during every 60 minutes of continuous operation.
Table 13
Cooling/dehumidification load status response
1-Step Cooling Only
Dehumidifying Only
1-Step Cooling w/ Dehumidifying
* See 4.2.3 - Dehumidification Operation.
GLYCOOL Cooling
When GLYCOOL cooling is available, the temperature control will calculate a total cooling require-
ment of 200% rather than 100%. Assuming that full GLYCOOL capacity is available, the GLYCOOL
valve opens proportionally as the requirement for cooling rises from 0 to 100%. If more than 100%
cooling is required, then the compressor is activated at 200%. If full GLYCOOL capacity is not avail-
able, then the GLYCOOL valve will be opened proportionally over a cooling requirement band equal
to the available GLYCOOL capacity. The compressor would be activated at a cooling requirement of
100% above the available GLYCOOL capacity.
For example, if the GLYCOOL capacity is 60%, then the GLYCOOL valve would be full open at 60%
cooling requirement and the compressor would be in full cooling at 160%. In order to reduce compres-
sor cycling and prevent hunting, GLYCOOL capacity first becomes available when the entering glycol
temperature is at least 8°F (22% capacity) below the return air temperature, or 3°F below the return
air temperature for 2 hours. GLYCOOL capacity approaches 100% when the glycol temperature is 25
degrees F below the return air temperature. The system will continue to Econ-O-Cool as necessary as
long as the entering glycol temperature remains at least 3°F (0% capacity) below the return air tem-
perature. If GLYCOOL is not available, the temperature control will operate the compressor in the
same manner as a 1-step or 2-step system without GLYCOOL.
28

System Performance with Advanced Microprocessor Controls

A
M
DVANCED
ICROPROCESSOR
LLSV1
HGBP
On
On
On
On
On
On
C
ONTROLS
HGBP2
Low Fan Speed
Off
On
On*

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents