CHAPTER 3: INTERFACES
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
LOCKOUT: Red
Turns "ON" when the following elements are activated:
Thermal Overload
Short Circuit
Mechanical Jam
Ground Fault.
Can be reset only by emergency restart or lockout reset, if they are enabled.
If the above are not enabled, a normal reset will turn the LED "OFF".
START INHIBIT: Red
Turns "ON" when the Start Inhibit element is activated.
Self-resetting when the inhibit is no longer present.
STOPPED: Default to Red
LED color is programmable. Turns "ON" when the motor status is "Stopped".
STARTING: Default to Amber
LED color is programmable. Turns "ON" when the motor status is "Starting".
RUNNING: Default to Green
LED color is programmable. Turns "ON" when the motor status is "Running".
HOT RTD: Amber
Turns "ON" when either a RTD Alarm or Trip has been activated.
Self-resetting when the fault is no longer present.
FRONT CONTROL PANEL INTERFACE