S3 PROTECTION
6–122
OUTPUT RELAY 4 to 6 / OUTPUT RELAY 5 to 6
Range: Do Not Operate, Operate
Default: Do Not Operate
Any assignable output relay can be selected to operate upon High Speed Undercurrent
operation. When the SWITCHING DEVICE is selected as BREAKER, the assignable output
relays will be Output Relay 4 to 6. When the SWITCHING DEVICE is selected as
CONTACTOR, the assignable output relays will be Output Relay 5 to 6.
BLOCK 1 to 3
Range: Off, Contact Input 1 to 10, Virtual Input 1 to 32, Remote Input 1 to 32, Logic
Element 1 to 16
Default: Off
Three blocking inputs are provided for the High Speed Undercurrent function. When any
of the selected blocking inputs is on, the High Speed Undercurrent is blocked.
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: SETPOINTS