S3 PROTECTION
6–112
S3 RTD #1
RTD #1 APPLICATION
Stator
RTD #1 NAME
RTD1
RTD #1 ALARM
Enabled
RTD #1 ALARM TEMP
°
130 C
RTD #1 TRIP
Disabled
RTD #1 TRIP TEMP
°
155 C
RTD #1 TRIP VOTING
Off
OUTPUT RELAY 4
Do Not Operate
OUTPUT RELAY 5
Do Not Operate
OUTPUT RELAY 6
Do Not Operate
BLOCK 1
Off
BLOCK 2
Off
BLOCK 3
Off
896802.cdr
BLOCK 1 to 3
Range: Off, Contact Input 1 to 10, Virtual Input 1 to 32, Remote Input 1 to 32, Logic
Element 1 to 16
Default: Off
Three blocking inputs are provided for RTD Protection. When any of the selected blocking
inputs is on, both RTD Alarm and Trip functionalities are blocked.
S4 LOGIC ELEMENT 1
LOGIC E 1 NAME
Alarm Operation
LOGIC E1 FUNCTION
Enabled
LOGIC E1 ASSERTED
On
TRIGGER SOURCE 1
Any Alarm OP
TRIGGER SOURCE 2
Off
TRIGGER SOURCE 3
Off
PICKUP TIME DELAY
0 ms
DROPOUT TIME DELAY
0 ms
OUTPUT RELAY 4
Do Not Operate
OUTPUT RELAY 5
Operate
OUTPUT RELAY 6
Do Not Operate
BLOCK 1
Off
BLOCK 2
Off
BLOCK 3
Off
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: SETPOINTS