Technical Data; Selection And Ordering Data - Siemens 3RW44 Manual

Industrial control soft starters
Hide thumbs Also See for 3RW44:
Table of Contents

Advertisement

11.3

Technical data

11.3.1

Selection and ordering data

Table 11- 1
Normal starting (CLASS 10) in inline circuit - Part 1/3
Ambient temperature 40 ℃
Rated
Rated
Rated power of three-phase
operation-
opera-
motors at rated operational
al voltage
tional
voltage U
U
current
e
I
e
230 V
V
A
kW
200 ... 460 29
5.5
36
7.5
47
11
57
15
77
18.5
93
22
400 ... 600 29
-
36
-
47
-
57
-
77
-
93
-
400 ... 690 29
-
36
-
47
-
57
-
77
-
93
-
x
1 = screw-type terminals, 3 = spring-loaded terminals
1
3RW44 soft starters
Manual, 03/2017, NEB535219502000/RS-AB/008
e
400 V
500 V
690 V
kW
kW
kW
15
-
-
18.5
-
-
22
-
-
30
-
-
37
-
-
45
-
-
15
18.5
-
18.5
22
-
22
30
-
30
37
-
37
45
-
45
55
-
15
18.5
30
18.5
22
37
22
30
45
30
37
55
37
45
75
45
55
90
Ambient temperature 50 ℃
Rated
Rated power of three-phase
opera-
motors at rated operational
tional
voltage U
e
current
I
e
200 V
230 V
A
HP
HP
26
7.5
7.5
32
10
10
42
10
15
51
15
15
68
20
20
82
25
25
26
-
-
32
-
-
42
-
-
51
-
-
68
-
-
82
-
26
-
-
32
-
-
42
-
-
51
-
-
68
-
-
82
-
-
General technical data
11.3 Technical data
Article No.
460 V
575 V
HP
HP
15
-
3RW44 22-x
20
-
3RW44 23-x
25
-
3RW44 24-x
30
-
3RW44 25-x
50
-
3RW44 26-x
60
-
3RW44 27-x
15
20
3RW44 22-x
20
25
3RW44 23-x
25
30
3RW44 24-x
30
40
3RW44 25-x
50
50
3RW44 26-x
60
75
3RW44 27-x
15
20
3RW44 22-x
20
25
3RW44 23-x
25
30
3RW44 24-x
30
40
3RW44 25-x
50
50
3RW44 26-x
60
75
3RW44 27-x
BCx
4
1
2
BCx
4
1
2
BCx
4
1
2
BCx
4
1
2
BCx
4
1
2
BCx
4
1
2
BCx
5
1
2
BCx
5
1
2
BCx
5
1
2
BCx
5
1
2
BCx
5
1
2
BCx
5
1
2
BCx
6
1
2
BCx
6
1
2
BCx
6
1
2
BCx
6
1
2
BCx
6
1
2
BCx
6
1
2
253