The Setting Range Of The Capacity Of Each Area - Mitsubishi Electric FX5 User Manual

Melsec iq-f series
Hide thumbs Also See for FX5:
Table of Contents

Advertisement

13.2

The Setting Range of the Capacity of Each Area

The setting range of the capacity of each area on the device/label memory is as follows.
Item
Device (high speed) Area Capacity
Device (standard) Area Capacity
Label Area Capacity
Latch Label Area Capacity
Restriction of a label/latch label area capacity
■When device area setting using by label/latch label is standard area
Label Area Capacity + Latch Label Area Capacity + Device (standard) Area Capacity ≤ 48 K Word (1 K word unit)
■When device area setting using by label/latch label is high speed area
Label Area Capacity + Latch Label Area Capacity + Device (high speed) Area Capacity ≤ 12 K Word (1 K word unit)
■When FB is used
When using FB, the reserved area for adding labels other than the labels defined for FB will be used.
The following capacities are consumed per FB instance.
Label area: 48 words
Latch area: 16 words
Setting range of capacity of each area
0 to 12 K words
0 to 48 K words
0 to 48 K words
0 to 48 K words
13 DEVICE/LABEL MEMORY AREA SETTING
13.2 The Setting Range of the Capacity of Each Area
13
111

Advertisement

Table of Contents
loading

Table of Contents