Wiring Diagrams

Figure 3-1. PlantWeb Wiring
(4–20 mA)
Figure 3-2. Junction Box Wiring
(4–20 mA)
Bench Hook-up
Connect the bench equipment as shown in Figures 3-1 and 3-2, and turn on
the HART Communicator by pressing the ON/OFF key or log into AMS. The
HART Communicator or AMS will search for a HART-compatible device and
indicate when the connection is made. If the HART Communicator or AMS fail
to connect, it indicates that no device was found. If this occurs, refer to
Section 5: Troubleshooting.
Field Hook-up
Figures 3-1 and 3-2 illustrate wiring loops for a field hook-up with a HART
Communicator or AMS. The HART Communicator or AMS may be connected
at "COMM" on the transmitter terminal block, across the load resistor, or at
any termination point in the signal loop. Signal point may be grounded at any
point or left ungrounded.
Rosemount 3051S Series
Power Supply
RL ≥ 250 Ω
Power Supply
RL ≥ 250 Ω
3-3